期刊文献+

330kV换流站隔离开关静触头失效原因分析 被引量:6

Failure Cause Analysis on Disconnector Static Contact of 330 kV Converter Station
下载PDF
导出
摘要 采用宏观检验、化学成分分析、厚度和硬度检测法对失效静触头进行了分析,认为触头失散是由镀层质量不佳、压缩弹簧失效和触头结构不合理等共同因素造成的。针对分析结果,提出应加强高压隔离开关静触头触指的入厂检验,确保各项指标符合要求,并定期巡视其使用情况。 The conductive contact is an important component of high-voltage opening switch device,and can impact the safe operation of the device directly. The paper analyzes static contact failure by means of some methods such as macroexamination, chemical elements analysis as well as thickness and hardness test.The resuhs show that the contact failure is caused by poor quality coating, compression spring failure and unreasonable contact structure. Based on which, the paper proposes preventive measures that strengthen the incoming inspection of HV disconnector static contact and regularly check its working state.
出处 《陕西电力》 2012年第12期72-74,共3页 Shanxi Electric Power
关键词 静触头 镀层质量 压缩弹簧 触头结构 static contact coating quality compression spring contact structure
  • 相关文献

参考文献5

  • 1中国电力出版社.高压开关设备管理规范[M]北京:中国电力出版社,2006.
  • 2中华人民共和国质量监督检验检疫总局.GB/T4340-2009,金属材料维氏硬度试验[S].
  • 3刘建军,杨庆旭.高压开关设备镀银层硬度检测技术介绍[J].江苏电机工程,2010,29(6):83-84. 被引量:6
  • 4范志康;梁淑华;肖鹏.高压点触头材料[M]北京:机械工业出版社,2004.
  • 5李建基.高压开关设备实用技术[M]北京:中国电力出版社,2005.

二级参考文献2

  • 1中华人民共和国质量监督检验检疫总局.GB/T.4340--2009金属材料维氏硬度试验[S].
  • 2中华人民共和国质量监督检验检疫总局.GB/T18449--2009金属材料努氏硬度试验[S].