期刊文献+

一种特高压直流输电线路单端电压暂态保护原理 被引量:21

The principle of single-ended transient based voltage protection for UHVDC transmission line
下载PDF
导出
摘要 平波电抗器、直流滤波器、PLC滤波器构成特高压直流输电线路现实边界。分析特高压直流输电线路边界以及特高压直流输电线路的频率特性,研究特高压直流输电线路以及边界对故障暂态电压信号高频量的衰减作用。分析现有特高压直流输电线路暂态保护原理的保护范围,指出现有利用保护元件区分本侧区内外故障的特高压直流输电线路暂态保护原理并不能实现特高压直流输电线路全线保护。综合考虑特高压直流输电线路边界和线路对故障暂态信号高频量的衰减作用,提出利用保护元件区分对侧区内外故障的特高压直流输电线路单端电压暂态保护原理。建立云广特高压直流输电系统实际参数仿真模型,对所提出的特高压直流输电线路单端电压暂态保护原理进行仿真验证。 The smoothing reactor, DC filter and PLC filter form the physical boundary of UHVDC transmission line. The frequency characteristics of UHVDC transmission line and line boundary are analyzed, and the attenuation of high frequency fault transient signal caused by UHVDC transmission line boundary and transmission line is studied. The protection area of transient based protection of UHVDC transmission line which is widely used now is analyzed, and it is concluded that the transient based protection method can not protect the whole transmission line. Considering the attenuation of high frequency fault transient signal caused by UHVDC transmission line boundary and transmission line, single-ended transient based voltage protection method of UHVDC transmission line which uses protector to distinguish the opposite inside fault from outside fault is studied. The actual parameter simulation model is built, and the single-ended transient based voltage protection method studied in this paper is simulated.
出处 《电力系统保护与控制》 EI CSCD 北大核心 2013年第3期26-31,共6页 Power System Protection and Control
基金 国家自然科学基金资助项目(50977039 51105183 51267008) 云南省应用基础研究基金项目(2010ZC050) 云南省教育厅科学研究基金项目(09Y0057)~~
关键词 特高压直流 线路边界 频率特性 单端电压暂态保护 频谱分析 UHVDC transmission line boundary frequency characteristic single-ended transient based voltage protection frequency analysis
  • 相关文献

参考文献9

二级参考文献63

共引文献330

同被引文献299

引证文献21

二级引证文献264

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部