期刊文献+

Corona noise model of high-voltage AC transmission lines and engineering applications

Corona noise model of high-voltage AC transmission lines and engineering applications
下载PDF
导出
摘要 In order to predict the levels of corona noise from high-voltage alternating current (AC) transmission lines,the mechanism of corona noise and the corresponding theoretical prediction model are investigated. On the basis of Drude model,the motion of positive and negative ions produced by high-voltage corona is analyzed,and the mechanism of corona noise is discovered. The theoretical prediction model is put forward by using Kirchhoff formula,which is verified by the well agreement between our result and others',considering the case of three-phase single lines. Moreover,the calculation results show that for both single and bundled lines,the sound pressure level of the typical frequency,i.e. twice the power frequency,attenuates slowly and leads to an obviously interferential phenomenon near the transmission lines,but the level of the bundled lines is smaller than that of the single ones under the same transmission voltage. Based on the mechanism of corona noise and the prediction model,it is obvious that bundled lines and/or increased line radius can be adopted to reduce corona noise in the practical engineering applications effectively. This model can also provide a theoretical guidance for the high-voltage AC transmission line design. In order to predict the levels of corona noise from high-voltage alternating current (AC) transmission lines, the mechanism of corona noise and the corresponding theoretical prediction model are investigated. On the basis of Drnde model, the motion of positive and negative ions produced by high-voltage corona is analyzed, and the mechanism of corona noise is discovered. The theoretical prediction model is put forward by using Kirchhoff formula, which is verified by the well agreement between our result and others' , considering the case of three- phase single lines. Moreover, the calculation results show that for both single and bundled lines, the sound pres- sure level of the typical frequency, i.e. twice the power frequency, attenuates slowly and leads to an obviously in- terferential phenomenon near the transmission lines, but the level of the bundled lines is smaller than that of the single ones under the same transmission voltage. Based on the mechanism of corona noise and the prediction model, it is obvious that bundled lines and/or increased line radius can be adopted to reduce corona noise in the practical engineering applications effectively. This model can also provide a theoretical guidance for the high-volt- age AC transmission line design.
出处 《Engineering Sciences》 EI 2013年第1期68-73,共6页 中国工程科学(英文版)
关键词 交流输电线路 噪声模型 电晕 应用 工程 预测模型 高压 基尔霍夫公式 corona noise Drude model twice power frequency component Kirchhoff formula noise reduction
  • 相关文献

参考文献3

二级参考文献41

  • 1吴桂芳.我国±500kV直流输电工程的电磁环境问题[J].电网技术,2005,29(11):5-8. 被引量:60
  • 2邬雄,万保权,路遥.1000kV级交流输电线路电磁环境的研究[J].高电压技术,2006,32(12):55-58. 被引量:66
  • 3唐剑,何金良,杨迎建,陈维江,邬雄,谷山强.特高压电晕笼防护段的设计[J].高电压技术,2007,33(3):17-20. 被引量:23
  • 4唐剑,杨迎建,何金良,陈维江,邬雄,谷山强.1000kV级特高压交流电晕笼设计关键问题探讨[J].高电压技术,2007,33(4):1-5. 被引量:37
  • 5Electric Power Research Institute.Transmission Line Reference Book 345 kV and Above, 2nd Edition[M]. Palo Alto, California: Electric Power Research Institute, 1987.
  • 6TAYLOR E R, CHARTIER V L, RICE D N. Audible Noiseand Visual Corona from HV and EHV Transmission Lines and Substation Conductors Laboratory Tests[J]. IEEE Transactions on Power Apparatus and Systems, 1969, 88 (5):666- 679.
  • 7COMBER M G, NIGBOR R J. Audible Noise Performance of Regular and Asymmetric Bundles and Effect of Conductor Aging on Project UHV's Three-phase Test Line [J]. IEEE Transactions on Power Apparatus and Systems, 1979, 98(2): 561-572.
  • 8VINH T, SHIH C H, KING J V,et al. Audible Noise and Corona Loss Performance of 9-conductor Bundle for UHV Transmission Lines[J]. IEEE Transactions on Power Apparatus and Systems, 1985, 104(10): 2764-2770.
  • 9LUNDQUIST J. Results from A.C Transmission Line Audible Noise Studies at the Anneberg EHV Test Station [J]. IEEE Transactions on Power Delivery, 1990, 5(1): 317-323.
  • 10LEKGANYANE M J, IJUMBA N M, BRITTEN A C. Corona Audible Noise Measurements in a Small Indoor Corona Cage under HVDC Voltages [C]// 2006 International Conference on Power System Technology, New York, USA, 2006: 1-5.

共引文献62