期刊文献+

通信电源SPD智能脱扣方法 被引量:2

Smart Disconnection Method for Telecommunication Power SPD
原文传递
导出
摘要 探讨了氧化锌压敏电阻SPD的传统脱扣方法的不足:脱扣不及时、不精确乃至误脱扣,以及低电压电源系统避雷器智能脱扣系统的要求与实现的难点,并设计了基于电流互感器数据差分方法在线检测压敏电阻漏电流和微控制器数据处理的智能脱扣方法,所述脱扣器动作准确及时,可长期复用。 The disadvantage - imprecise, untimely or even incorrect disconnecting - of traditional disconnection method of zinc oxide MOV SPD is discussed as well as the requirements and the difficulties on its fulfillment of the smart disconnecting system of low voltage power supply system arrester. A method of smart disconnection based on current leakage online measuring by current transformers data differential method and MCU differential data processing is designed. The mentioned smart disconnecting system can act timely and precisely, and is reusable over time.
作者 胡勇坚
机构地区 台州学院
出处 《电瓷避雷器》 CAS 北大核心 2013年第1期79-83,共5页 Insulators and Surge Arresters
基金 台州市高校教育科学规划研究课题(编号:GG12008)
关键词 SPD 智能脱扣器 劣化保护 SPD smart disconnection protection for degradation
  • 相关文献

参考文献10

  • 1杨小平,李盛涛,张磊.基于RS-485总线的金属氧化物避雷器在线监测系统的研究[J].电瓷避雷器,2003(5):29-33. 被引量:16
  • 2胡勇坚.通信电源防雷器自脱扣原理的研究[J].电瓷避雷器,2005(1):29-31. 被引量:2
  • 3国际电工技术委员会.电压系统电涌保护器第一部分电涌保护器的技能要求及测试方法[S],1998.
  • 4国际电工技术委员会.低压系统的电涌保护器,第2部分选择和使用原理(在低压配电系统中)[S],1997.
  • 5邵慧丽.电压谐波对MOA泄漏电流检测方法影响分析[J].电瓷避雷器,2012(1):94-98. 被引量:11
  • 6中讯邮电咨询设计院(原信息产业部邮电设计院);艾默生网络能源有限公司;广东省电信公司科学技术研究院(中国电信集团广州研发中心).通信局(站)低压配电系统用电涌保护器测试方法[S]北京:中华人民共和国信息产业部,2002.
  • 7广东省电信公司科学技术研究院(中国电信集团广州研发中心);中讯邮电咨询设计院(原信息产业部邮电设计院).通信局(站)低压配电系统用电涌保护器技术要求[S]北京:中华人民共和国信息产业部,2002.
  • 8北京市气象局;广东省气象局;上海市气象局.电涌保护器第一部分:性能要求和试验[S]中国气象局,2002.
  • 9国际电工技术委员会.第3部分电涌保护器(SPD)的要求(草案)[S],1996.
  • 10张育华,李凡,桑建平.线路避雷器的应用及监测[J].电瓷避雷器,2006(4):30-33. 被引量:17

二级参考文献30

  • 1常越,钱家骊.LCD-4仪器检测三相氧化锌避雷器阻性电流的分析[J].高电压技术,1995,21(2):77-80. 被引量:21
  • 2李红蕾,桑建平,姜伟军,李亚东.浅析MOA泄漏电流测试方法[J].电瓷避雷器,2006(2):40-43. 被引量:31
  • 3LUNDQUIST J. New Method for Measurement of the resistive leakage currents of metal-oxide surge arrdsters in ser- vice [J]. IEEE Transaction on Power Delivery, 1990, 5 (5): 1811-1822.
  • 4Heinrieh C,Hinrinehsen V. Diagnostics and monitoring of metal-oxide surge arrester in high-voltage networks-comparison of existing and newly developed proeedures [J ]. IEEE Trans. On Power Delivery, 2001,16(1) :138-143.
  • 5Shi Bao-zhuang,Li Yang, An investigation on the influencing factors on on-line insulation monitoring of HV apparatus [J] .Conference Record of the 2000IEEE International Symposium on Electrical Insulation, Anaheim ,CA USA, 2000-04 : 81 - 84.
  • 6Yan Xiang-lian, Wen Yuan-fang ,Yi Xiao-yu. Study on the resistive leakage current characteristic of MOV surge arresters [ J ] .IEEE Transmission and Distribution Conference and Exhibition 2002: AsiaPacific. IEEE/PES, 2002-10,2 : 683 - 687.
  • 7Li Yan-yong, Li Sheng-tao, Li Lei, Liu Fu-yi. An automatic measuring device based on PC for MOVs'aging test[J]. Properties and Applications of Dielectric Materials, 2000. Proceedings of the 6th International Conference on, 2000-06,2: 1026 - 1028.
  • 8洪贞贤,金向朝.电容器组CT保护用避雷器爆裂原因分析[J].电力电容器与无功补偿,2008,29(5):51-53. 被引量:35
  • 9葛猛,韩学坤,陶安培.金属氧化物避雷器阀片老化缺陷的诊断及原因分析[J].高压电器,2009,45(3):145-147. 被引量:59
  • 10梁义明,付浩,邵涛.吉林省66kV及220kV输电线路防雷措施及应用效果分析[J].电瓷避雷器,2009(5):36-40. 被引量:8

共引文献42

同被引文献24

  • 1胡勇坚.通信电源防雷器自脱扣原理的研究[J].电瓷避雷器,2005(1):29-31. 被引量:2
  • 2尹天文,王碧云,蒋容兴.电涌保护器脱离器的设计与研究[J].低压电器,2006(8):3-7. 被引量:7
  • 3任晓明,蔡振新,傅正财.低压电涌保护器暂态过电压测试方法研究[J].高压电器,2007,43(4):248-249. 被引量:18
  • 4杨大晟,张小青,许杨.低压供电系统中SPD的失效模式及失效原因[J].电瓷避雷器,2007(4):43-46. 被引量:29
  • 5上海电器科学研究所;西安电瓷研究所;中国国家标准化管理委员会.低压配电系统的电涌保护器(SPD)第1部分:性能要求和试验方法[S]{H}北京:中国标准出版社,2012.
  • 6广东省电信公司科学技术研究院.(站)低压配电系统用电涌保护器技术要求[S]北京:中华人民共和国信息产业部,2002.
  • 7北京市气象局;广东省气象局;上海市气象局.电涌保护器第一部分:性能要求和试验[S]北京:中国气象局,2002.
  • 8西安电瓷研究所;贵州飞舸电子有限公司;中国国家标准化管理委员会.低压电涌保护器元件第331部分:金属氧化物压敏电阻(MOV)规范[S]{H}北京:中国标准出版社,2008.
  • 9胡勇坚;程小辉.一种智能电源避雷器[P]中国,ZL20071010434282007.
  • 10上海电气科学研究所;西安电瓷研究所;中国国家标准化管理委员会.低压配电系统的电涌保护器(SPD)第1部分:性能要求和试验方法[S]{H}北京:中国标准出版社,2002.