导出
摘要 某电子集团采用电吸附除盐技术对循环冷却水外排水进行除盐处理,试验结果表明,在原水电导率平均为2 243.5μS/cm、硬度平均为1 161.7mg/L、氯离子平均为396.1mg/L的情况下,产水电导率平均为716.5μS/cm、硬度平均为449.1mg/L、氯离子平均为118.3mg/L,平均去除率分别为68.1%、61%和71.2%;单位水量能耗为1.34kW.h;产水率大于75%。可达《城市污水再生利用工业用水水质》(GB/T 19923—2005),电吸附除盐技术应用于电子行业循环冷却水除盐处理是可行的。 The Electro-adsorbtion process was applied in desalinating the discharged recirculat- ing cooling water in an electronic group. The experiments showed that when the average conductivity of effluent was 2 243. 5μS/cm, average hardness was 1 161.7 mg/L, and concentration of chloride was 396. 1 mg/L, the average conductivity of influent was 716.5 /,S/cm, hardness was 449.1 mg/L, and average chloride concentration was 118. 3 mg/L; the average removal rates were 68. 1%,61% and 71.2% respectively, unit flow energy consumption is 1.34 kW % h, the water production capability was more than 75 %. The drainage could meet the requirements of The reuse of urban recycling water-water quality standard for industrial uses (GB/T 19923--2005). There-fore Electro-adsorbtion process is feasible for desalination of recirculating cooling water treatment in electronic industry.
作者 高远
出处 《给水排水》 CSCD 北大核心 2013年第3期51-53,共3页 Water & Wastewater Engineering
关键词 电吸附技术 循环冷却水 除盐 电子行业 Electro- adsorbtion technology Recirculating cooling water Desalination Electronic industry
  • 相关文献

参考文献5

  • 1孙晓慰,朱国富.电吸附水处理技术及设备[J].工业水处理,2002,22(8):1-3. 被引量:54
  • 2陈兆林,孙晓慰,朱广东,郭洪飞,宋存义.电吸附设备工作过程的研究[J].环境工程学报,2009,3(7):1307-1310. 被引量:14
  • 3查全性.电极过程动力学导论[M]{H}北京:科学出版社,2002.
  • 4Zhang D S,Shi L Y,Fan J H. Removal of NaCl from salt water solution using carbon nanotubes/activated carbon composite electrodes[J].{H}Materials Letters,2006.360-363.
  • 5Li L X,Zou L D,Song H H. Ordered mesoporous carbons synthesized by a sol-gel process for electrosorptive removal of sodium chloride[J].{H}CARBON,2009.775.

二级参考文献8

  • 1Soldatov V. S. , Sokolova V. I. , Medyak G. V. , et al. Binary ion exchange equilibria in systems containing NO3^- , Cl^- and SO4^2- on fibrous anion exchangers with tetraalkylammomium groups. Reactive & Functional Polymers, 2007, 67:1530 - 1539.
  • 2Mohammad A. S. , Hisham E. Developments in thermal desalination processes: Design, energy, and costing aspects. Desalination, 2007, 214: 227- 240.
  • 3Laura J. B. , Thomas W. J. , Andrea I. Desalination using electrodialysis as a function of voltage and salt concentration. Desalination, 2007, 205 : 38 - 46.
  • 4Goztilivez J. M. , Lora J. , Mendoza J. A. , et al. Modeling of a low-pressure reverse osmosis system with concentrate recirculation to obtain high recovery levels. Desalination, 2002, 144:341 - 345.
  • 5Helal A. M. , El-Nashar A. M. , Al-Katheeri E. , et al. Optimal design of hybrid RO/MSF desalination plants, Part I: Modeling and algorithms. Desalination, 2003, 154:43-66.
  • 6Khaled W., Raja B. A., Loubna F., et al. Brackish groundwater treatment by nanofiltration, reverse osmosis and electrodialysis in Tunisia: Performance and cost comparison. Desalination, 2007, 207:95 - 106.
  • 7Bard A. J., Faulkner L. R. Electrochemical Methods:Fundamentals and Applications. New York: John Wiley & Sons, 2000. 583.