期刊文献+

基于DDA和PDA模型的供水管网管段重要性计算研究 被引量:1

Comparative study of calculation methods for link importance in water distribution network based on DDA and PAD models
下载PDF
导出
摘要 介绍了如何确定单管段故障状况下供水管网满足用户的供水比例,根据两种管网水力分析模型:需水量驱动分析(DDA)模型和考虑管网节点压力与实际出流量关系的压力驱动分析(PDA)模型,并引入管段重要性的概念,提出编制管段重要性计算程序的步骤。通过案例分析两种模型,结果表明在管网压力不足情况下,采用PDA模型计算管段重要性值更具合理性。 It is of great importance to determine supply proportion under a pipe failure event for the operation and administration of water distribution systems. According to the definition of link importance (LI), a method of computer programming is proposed based on two different distribution network hydraulic analysis models: Demand-driven analysis (DDA)model and Pressure-driven aalysis (PDA) model in this paper, while the latter combines the relationship between nodal pressure and outflow. A network example is used for two models to analysis, the results show that the LI values from PDA model is more reasonable in situation when the network pressure is insufficient.
出处 《给水排水》 CSCD 北大核心 2013年第3期154-157,共4页 Water & Wastewater Engineering
基金 国家水体污染控制与治理科技重大专项(2012ZX07403-001)
关键词 供水管网 管段重要性(LI) 需水量驱动分析(DDA) 压力驱动分析(PDA) Water distribution network Link importance (LI) Demanddriven analysis (DDA) Pressure-driven analysis(PDA)
  • 相关文献

参考文献10

  • 1Wu Z Y,Wang R H,Walski T M. Extended global-gradient algorithm for pressure-dependent water distribution analysis[J].{H}Journal of Water Resources Planning and Management,2009,(1):13-22.doi:10.1061/(ASCE)0733-9496(2009)135:1(13).
  • 2Siew C,Tanyimboh T T. Pressure-Demandent EPANET Extension[J].{H}Water Resources Management,2012,(6):1477-1498.
  • 3Cheung P B,Van Zyl J E,Reis L F R. Extension of epanet for pressure driven demand modeling in water distribution system[A].Exeter,U.K,2005.
  • 4Goulter I,Walski T M,Mays L W. Reliability analysis for design[A].New York US,McGraw-Hill Companies Inc,2000.
  • 5Rossman L A. EPANETH2 Programmer's Toolkit[M].Environmental Protection Agency Risk Reduction Engineering Laboratory,Cincinnati,USA,2000.
  • 6Ang W K,Jowitt P W. Solution for water distribution systems under pressure-deficient conditions[J].Journal of Water Resources Planning and Management ASCE,2006,(3):175-182.
  • 7Kalungi P,Tanyimboh T T. Redundancy model for water distribution systems[J].Reliability Engineering and System Safety,2003,(3):275-286.
  • 8Pathirana A. Epanet2 desktop application for pressure driven demand modeling[A].Cincinnati,Ohio,USA,2010.
  • 9Rossman L A. EPANETH2 user manual[M].Environmental Protection Agency Risk Reduction Engineering Laboratory,Cincinnati,USA,2000.
  • 10严煦世;刘遂庆.给水排水管网系统[M]{H}北京:中国建筑工业出版社,2008.