期刊文献+

基于三次谐波相角突变原理的发电机定子接地保护 被引量:10

A GENERATOR GROUNDING FAULT PROTECTION BASED ON PHASE-ANGLE MUTATION OF THIRD HARMONIC VOLTAGE
下载PDF
导出
摘要 提出了基于 3次谐波相角突变原理的发电机定子接地保护及其算法 ,用数字仿真方法分析了灵敏度并和其它原理的微机保护方案作了比较 ,结果表明该原理适用于各种接地方式的大型汽轮发电机 ,并且灵敏度很高。同时 ,还具有可靠性高。 On thebasis of thetheoryof phase\|angle mutation of third harmonicvoltage a protection scheme forgenerator statorgrounding faultand its algorithm are put forward. This scheme is comparedwith micro\|computer protectiveschemes based on otherprotectionprinciples, comparison result shows that this scheme is applicable for large capacity generator with all kinds of grounding system, especially it is of high sensitivity under arc suppression coil grounding or non\|grounding. Otherwise, This scheme possesses high reliability, and is not prone to affected by surge suppressors installed at the terminals of large generator.
出处 《电网技术》 EI CSCD 北大核心 2000年第12期70-73,共4页 Power System Technology
关键词 汽轮发电机 定子 接地保护 相角突变原理 谐波 generator stator grounding fault protection third harmonic phase-angle mutation
  • 相关文献

参考文献3

二级参考文献6

共引文献19

同被引文献57

引证文献10

二级引证文献28

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部