期刊文献+

变电站电压无功控制对静态电压稳定的影响分析 被引量:8

Analysis of the impact of voltage and reactive power control in substations on steady state voltage stability
下载PDF
导出
摘要 变电站电压无功控制(VQC)通过在线监视负荷侧电压和高压侧注入无功来决定站内电容器电抗器的投切和主变抽头的调整,它是一种提高电压质量的重要手段。根据变电站VQC模块的九区控制图规则,建立考虑VQC动作的连续潮流计算模型,分析其对广东电网静态电压稳定性的影响,并观察到一种由VQC策略中OLTC动作引起的电压失稳分岔情况,称为OLTC调节诱导分岔。通过对广东电网的仿真分析表明,VQC调控能够维持变电站电压质量,提高静态电压稳定负荷裕度,但在重负荷条件下可能发生由于VQC的动作而引起的系统分岔,从而导致电压失稳。 Voltage and reactive power control (VQC) of substation determines capacitors or reactors switching and on-load tap changers (OLTC) automatically by on-line monitoring the load side bus voltage and high-voltage side reactive power injection. It is an important measure of maintaining voltage quality of power grid. According to nine-areas control diagram rule of substation VQC, this paper establishes a continuation power flow model including actions of VQC, and analyzes the impact of substation VQC on steady state voltage stability of Guangdong Power Grid. And a new type of bifurcation induced by OLTC regulation is founded, and it is called OLTC regulation induced bifurcation. A test on Guangdong Power Grid illustrates that VQC action can maintain voltage quality of substations and enhance steady state voltage stability margin, but may induce system bifurcation under heavy loading conditions, and lead to voltage collapse.
出处 《电力系统保护与控制》 EI CSCD 北大核心 2013年第7期103-108,共6页 Power System Protection and Control
基金 国家自然科学基金项目(51207056) 广东高校优秀青年创新人才培养计划项目(LYM11014) 中央高校基本科研业务费专项资金资助项目(2011ZM0021) 广东省绿色能源技术重点实验室资助项目(2008A060301002)~~
关键词 变电站无功电压控制 静态电压稳定 连续潮流 OLTC 调节诱导分岔 voltage and reactive power control of substations steady state voltage stability continuation power flow on-load tapchanger regulation induced bifurcation
  • 相关文献

参考文献18

二级参考文献109

共引文献307

同被引文献91

引证文献8

二级引证文献47

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部