500kV架空输电线路次档距振荡原因分析及防范措施 被引量:4

Subspan Oscillations Causes for 500 kV Overhead Transmission Line and Its Precautions
下载PDF
导出
摘要 针对呼伦贝尔地区500 kV架空输电线路发生次档距振荡问题进行分析,确定原因是由于导线间隔棒次档距设计值偏大,在风作用下导线产生次档距振荡。根据现场实际情况,对线夹回转式间隔棒采取不等距、不对称的布置方式,控制最大次档距不大于50 m,端次档距不大于25 m,平均次档距为45 m左右。调整安装后导线次档距振荡现象消失,效果较好。 Make analysis on the causes of subspan oscillations occurred at 500 kV overhead transmission line in Hulun Buir. The cause is the design value of conductor spacer subspan is larger, which leads to conductor subspan oscillation by wind. Based on the actual condition, the clip rotary spacer should be allocated in unequally and unsymmetrical way. The maximum subspan should be controled within 50 m, and the end subspan within 25 m. The average subspan is around 45 m. The subspan oscillations disappeared after the adjustment to the conductor subspan.
出处 《内蒙古电力技术》 2013年第1期43-45,共3页 Inner Mongolia Electric Power
关键词 500 kV架空输电线路 次档距振荡 次档距 线夹回转式间隔棒 布置方式 500 kV overhead transmission line subspan oscillations subspan cliprotary spacer allocation
  • 相关文献

参考文献3

  • 1郭应龙,李国兴,尤传永.输电线路舞动[M].北京:中国电力出版社,2002.
  • 2周振山.线路设计[M].北京:中国电力企业联合会教育培训部,1988:41.
  • 3东北电力设计院,内蒙古电力勘测设计院.呼辽直流送端电源送出工程防舞设计分析报告[R].呼和浩特:内蒙古电力勘测设计院,2012:3.

共引文献45

同被引文献12

  • 1郭应龙,李国兴,尤传永.输电线路舞动[M].北京:中国电力出版社,2002.
  • 2国家电网公司.国家电网公司十八项电网重大反事故措施(修订版)[M].北京:中国电力出版社,2012.
  • 3全国电力架空线路标准化技术委员会线路运行分技术委员会.DL/T741-2010架空输电线路运行规程[S].北京:中国电力出版社,2010.
  • 4东北电力大学.架空输电线路运行与检修[R].吉林:东北电力大学,2011:41.
  • 5国家电力公司电力规划设计总院.DL/T5092-1999110~500kV架空送电线路设计技术规程[s].北京:中国电力出版社,1999:41.
  • 6王秋梅,金伟君,程一呜,等.配电线路[M].北京:中国电力出版社,2012:32.
  • 7金西平.微地形微气候对输电线路覆冰的影响[C]//CIGRE中国国家委员会,中国电机工程学会咱然灾害对电力设施的影响与应对研讨会.北京:中国电力出版社,2008:2-17.
  • 8郑仟.750kV线路分裂导线次档距振荡机理及抑制措施[J].宁夏电力,2010(3):20-22. 被引量:12
  • 9朱大林,马超,代生丽.输电线路多分裂导线次档距振荡分析[J].陕西电力,2012,40(11):43-45. 被引量:2
  • 10祝永坤,刘福巨,江柱.微地形微气象地区输电线路风偏故障分析及防范措施[J].内蒙古电力技术,2014,32(2):11-14. 被引量:6

引证文献4

二级引证文献13

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部