摘要
介绍了国电电力大连开发区热电厂二期发电机直流泄漏试验的初步分析.主要包括双水内冷发电机直流泄漏试验的理论依据、基本要求、试验器材、试验方法步骤、数据分析等.理论依据部分对绝缘试验、泄漏电流试验、绝缘缺陷等进行了解释,并阐述了试验的原理、试验意义.基本要求中主要阐述了此试验的注意事项以及仪器、技术要求.试验方法步骤部分说明了试验所需的仪器及其使用方法,包含此试验的全过程以及注意事项.数据分析部分针对试验可能出现的干扰因素,进行了深入的技术分析.
This paper introduces the technique used in dc leakage test of the generator and analysis of the tested data in the Dalian development zone thermal powe.r plant of Guodian Power Corporation. The paper mainly illustrates the the- oretical basis of dc leakage test in double-water internal cooling generator, basic requirements, test equipment, test methods and procedures, data analysis, etc. The test data shows that the leakage current of the generator is higher than the normal value, and three phase leakage current appears fluctuating. According to the test data and its analysis, this paper puts forward the improvement measures as the technology support to ensure the economical operation and safety of the generator.
出处
《沈阳工程学院学报(自然科学版)》
2013年第1期58-61,共4页
Journal of Shenyang Institute of Engineering:Natural Science