期刊文献+

感应发电机接入配网对闪变衰减效应的分析及计算

Analysis and Calculation of Flicker Attenuation Effect for Induction Generator Integrated Into Distribution Network
下载PDF
导出
摘要 感应发电机(induction generator,IG)接入配网时,不同频率的电网电压波动将使IG表现出动态变化的阻抗特性。首先分析IG接入配网对电压闪变的动态响应,定义IG电压波动衰减系数;重点比较柴油、风力等不同传动轴系对IG电压闪变衰减效应的影响,建立采用两质量块轴系的IG机组线性化模型,提出IG动态阻抗和电压波动衰减系数解析算法。利用Matlab/Simulink软件中IG的详细动态模型验证了本文提出方法的正确性,并分析了感应发电机闪变衰减效应的轴系参数灵敏度。 When induction generator (IG) is embedded in distribution network, its impedance characteristic will perform dynamic changes with the different voltage fluctuation frequencies. The dynamic response of IG to voltage flicker is observed, and the attenuation factor of voltage fluctuation is defined. The linearization model of IG with two-mass equivalent drive train is constructed according to the impact comparison of different drive trains to the voltage flicker attenuation, such as diesel engine, wind turbine and so on. Then an analytical method for IG integration into distribution network to determine the dynamic impedance and attenuation factor of voltage fluctuation is proposed. The correctness of proposed method is verified by the dynamic simulation using the detailed model of IG set in Matlab/Simulink software, and the sensitivity of drive train parameters to the voltage flicker attenuation effect oflG set is analyzed.
出处 《中国电机工程学报》 EI CSCD 北大核心 2013年第10期128-136,9,共9页 Proceedings of the CSEE
基金 输配电装备及系统安全与新技术国家重点实验室自主研究项目(2007DA10512711209)~~
关键词 闪变 闪变衰减 鼠笼式感应发电机 传动轴系 flicker flicker attenuation squirrel-cage rotor induction generator (IG) drive train
  • 引文网络
  • 相关文献

参考文献18

  • 1Eghtedarpour N, Farjah E, Khayatian A. Intelligent identification of flicker source in distribution systems[J]. IET Generation, Transmission and Distribution, 2010, 4(9): 1016-1027.
  • 2Barahona B, Srensen P, Christensen L, et al. Validation of the standard method for assessing flicker from wind turbines[J]. IEEE Transactions on Energy Conversion, 2011, 26(1): 373-378.
  • 3Horton R, Haskew T A. Determination of flicker transfer coefficients near large synchronous generators[J]. IEEE Transactions on PowerDelivery, 2010, 25(1): 260-269.
  • 4Akhmatov V. Induction generators for wind power[M]. Essex: Multi Science Press, 2007: 1-45.
  • 5Perera S, Robinson D, Elphick S, et al. Synchronized flicker measurement for flicker transfer evaluation in power systems[J]. IEEE Transactions on Power Delivery, 2006, 21(3): 1477-1482.
  • 6Hort0n R, Haskew T A. Effect of transfer coefficients on MV and LV flicker levels[J]. IEEE Transactions onPower Delivery, 2011, 26(2): 632-639.
  • 7Tennakoon S, Perera S, Robinson D. Flicker attenuation-part I: Response of three-phase induction motors to regular voltage fluctuations[J]. IEEE Transactions on Power Delivery, 2008, 23(2): 1207-1214.
  • 8Tennakoon S , Perera S , Robinson D . Flickerattenuation-Part II: Transfer coefficients for regular voltage fluctuations in radial power systems with induction motor loads[J]. IEEE Transactions on Power Delivery, 2008, 23(2): 1215-1221.
  • 9Simoes M C, Deckmann S M. Flicker propagation and attenuation[C]//Proceedings of Tenth International Conference on Harmonics and Quality of Power. Rio de Janerio, Brazih IEEE, 2002: 644-648.
  • 10Renner H, Sakulin M. Flicker propagation in meshed high voltage networks[C]//Proceedings of Ninth International Conference on Harmonics and Quality of Power. Orlando, United states: IEEE, 2000: 1023-1028.

二级参考文献57

共引文献103

;
使用帮助 返回顶部