摘要
针对光伏发电系统中传统孤岛检测方法存在的诸多缺陷,提出一种以并网点高次谐波电压为特征量的孤岛检测方法。测量并网点谐波电压,用S变换法提取测量电压中包含的高次谐波电压分量,以此分量作为孤岛识别和检测指标,无需外加扰动,即可消除检测盲区。理想光伏发电并网系统进行的仿真证明,在IEEE.Std 1547规定的最差情况下,本方法进行的孤岛检测仍可快速、准确地检测到孤岛现象。
For traditional photovoltaic generation system islanding detection methods exist many defects,A new Islanding detection method is proposed,which need not plus disturbance and can eliminate non-detection zone(NDZ) by extracting the higher harmonic components from the S-transformation of point of common coupling(PCC) voltage.Based on IEEE Std.1547,Simulated verification of the proposed method is accomplished in the ideal photovoltaic grid system,which can be fast,accurate detection to the occurrence of islanding phenomenon.
出处
《南昌大学学报(理科版)》
CAS
北大核心
2013年第1期30-33,共4页
Journal of Nanchang University(Natural Science)
基金
江西省科技厅攻关资助项目(2008S00262)
江西省教育厅科技资助项目(2009S00705)
关键词
光伏并网
孤岛检测
S变换
高次谐波
检测盲区
photovoltaic grid
islanding detection
S-transformation
high-order harmonic
non-detection zone