摘要
智能变电站二次试验系统与电网数字仿真系统相联接时,可能存在开关量信号不匹配的问题。针对该问题,本文介绍了两种解决方案,一种是外接模拟断路器的硬件方案,另一种是构建开关控制回路模型的软件方案,并以试验为例验证了以上两种方案的有效性。
There may be a switching signal mismatch problem in communication of the smart substation test system with the advanced digital power system simulator (ADPSS). Two methods are introduced in this paper to resolve the mismatch problem. One is a hardware solution by adding an analog breaker, and another is a software solution by designing a switch control circuit model. The feasibility of both methods are demonstrated in case studies on a realistic project.
出处
《湖北电力》
2013年第1期15-18,共4页
Hubei Electric Power
关键词
智能变电站
电网数字仿真系统
开关量信号
模拟断路器
smart substations
advanced digital power system simulator (ADPSS)
switching sig-nal
analog breaker