大管间距下地板辐射采暖的传热特性研究 被引量:1

Heat Transfer of Hydronic Radiant Heating System with Larger Tube Spacing
下载PDF
导出
摘要 我国现行规范规定:低温地板辐射供暖加热管最大铺设间距不宜超过300mm。但是,随着建筑外保温等技术的进步,按目前规范要求完成的设计,在运行中常出现房间过热现象。房间过热不仅使地板采暖的舒适性降低,而且也浪费了能源。本文研究了大管间距下地板辐射采暖的传热特性,以期通过合理增大埋管间距减少过热现象,降低系统投资,减少运行能耗。研究结果表明:多数情况下大管间距能够满足房间负荷要求。室内设计温度低于等于20℃、供回水平均温度大于等于45℃且地面不能覆盖类似毛毯等热阻较大的材料时可安全采用大管间距铺设。 It is specified in the manual for Design of Heating Ventilation and Air Conditioning of China that the tube spacing for hydronic underfloor heating system is not greater than 300mm. However, with improving thermal insulation performance of building envelope, the rooms are often overheated with the heating system. It results in not only the decrease of thermal comfort level but also the waste of energy. In this paper the heat-transfer of hydronic radiant floor heating with larger tube spacing has been studied in order to avoid overheating, decrease initial cost of hydronic system and reduce operational energy consumption. The results show that in most cases the system with larger tube spacing can meet load requirement. The suggestion is that the hydronic floor heating system with larger tube spacing is introduced when the design temperature for a room is lower than 20~C, the average temperature of the supply and return water is not less than 45~C and the floor is covered by any materials with large thermal resistance.
出处 《建筑热能通风空调》 2013年第1期15-19,共5页 Building Energy & Environment
关键词 大管间距地板辐射采暖传热特性 large tube spacing, hydronic radiant floor heating, heat transfer
  • 相关文献

参考文献9

二级参考文献24

  • 1杨杰,胡德秀,吴中如.大坝安全监控模型因子相关性及不确定性研究[J].水利学报,2004,35(12):99-105. 被引量:55
  • 2李长森.新旧采暖系统的比较[J].山西建筑,2005,31(13):154-155. 被引量:5
  • 3吴道闻,韩大建.因子相关性对大坝监测资料回归分析的影响[J].大坝观测与土工测试,1996,20(3):23-25. 被引量:11
  • 4Hoskuldsson A. PLS regression methods[J]. J Chemometrics, 1988, 2 (3): 211~228.
  • 5Eriksson L, Johansson E, Kettaneh-wold N, et al. Multi- and megavariate data analysis: Principles and applications[M]. Umea,Sweden: Umetrics Academy, 2001.
  • 6Schreiber T. Extremely simple nonlinear noise reduction method[J]. Phys Rev E, 1993, (47): 2401~2405.
  • 7Tenenhaus M. La Régression PLS:Théorie et pratique[A]. Document de Recherche de la Fondation HEC[C]. Jouy-en-Josas,Technip,Paris, 1997.
  • 8Palyulin V A , RadchenkoE V, Baranova O D, et al. MFTA: Recent Extensions of Molecular Field Topology Analysis: processes, problems and solutions[M], Blackwell Publishing, Bournemouth, UK, 2003. 188~190.
  • 9Georges R,Darbre. Probabilistic safety assessment of dams[A]. Papers of the 20th International Congress on Large Dams[C]. Beijing, China, 2000, Question 76: 185~195.
  • 10Berga L. Dam safety-proceedings of the international symposium on new trends and guidelines on dam safety[M]. Barcelona,Spain, A A Balkema Publishers, 1998.

共引文献106

同被引文献13

引证文献1

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部