期刊文献+

考虑配电网保护约束的IIDG准入容量及对策分析 被引量:5

Calculation of Penetration Level for Inverter Interfaced Distributed Generator Considering Protection in Distribution Network Constraints and Related Countermeasures
下载PDF
导出
摘要 逆变型分布式电源(IIDG)在系统故障时的输出特性与旋转电机有显著差异。考虑逆变器有限的过流能力建立了恒功率并网控制策略下的IIDG输出模型,定性分析配电网不同位置故障时IIDG的接入对继电保护可能的影响并推导含IIDG的短路电流计算公式。进而在保护配置不做出调整的条件下求得多个特定接入点处的IIDG的最大准入容量,并与未考虑过流限制的计算结果进行对比分析。为满足含高渗透率IIDG的复杂配电网保护需要,提出了一种配电网区域划分基础上的新型故障定位算法并借助算例进行了验证。 There are significant differences in output characteristics between inverter interfaced distributed generator(IIDG) and rotating machine when accidents occur in power system.An IIDG's output model was established based on PQ control strategy considering its limited overcurrent ability,and a qualitative analysis was made on IIDG's influence on relay protection and the short-circuit current calculation formulas containing IIDG was duduced.The maximum penetration level of different access point was obtained according to current protection's state and compared with the penetration level without considering overcurrent limit.To meet the demand of protection of complicated distribution network with high permeability IIDG,a new fault location algorithm was proposed based on zone division and verified by a case study.
出处 《中国电力》 CSCD 北大核心 2013年第3期47-52,共6页 Electric Power
关键词 逆变型分布式电源 恒功率控制 配电网 准入容量 区域划分 故障定位 inverter interfaced distributed generator(IIDG) PQ control distribution network penetration level zone division fault location
  • 相关文献

参考文献11

  • 1冯希科,邰能灵,宋凯,顾临峰,盛继卿.DG容量对配电网电流保护的影响及对策研究[J].电力系统保护与控制,2010,38(22):156-160. 被引量:82
  • 2王江海,邰能灵,宋凯,顾临峰,盛继卿.考虑继电保护动作的分布式电源在配电网中的准入容量研究[J].中国电机工程学报,2010,30(22):37-43. 被引量:122
  • 3陶顺,郭静,肖湘宁.基于电流保护原理的DG准入容量与并网位置分析[J].电网技术,2012,36(1):265-270. 被引量:43
  • 4NIMPITIWAN N, HEYDT G T, AYYANAR R, et al. Fault current contribution from synchronous machine and inverter based distributed generators[J]. Power Deiivery, 2007, 22(1): 634-641.
  • 5WANG Yu-bin, LAI Jih-sheng, LEE Yuang-Shuang, et al. Design of parallel inverters for smooth mode transfer micregrid applications [J]. IEEE Transactions on Power Electronics, 2010, 25(1): 6-15.
  • 6BARAN M E, EL-MARKABY I. Fault analysis on distribution feeders with distributed generators [J]. IEEE Trans on Power Systems, 2005, 20(4): 1757-1764.
  • 7孙景钌,李永丽,李盛伟,金强.含逆变型分布式电源配电网自适应电流速断保护[J].电力系统自动化,2009,33(14):71-76. 被引量:74
  • 8PLET C A, GRAOVAC M, GREEN T C, et ol. Fault response of grid-connected inverter dominated networks[C]//Power and Energy Society General Meeting. July 2010: 1-8.
  • 9PAN Y, REN W, RAY S, et ol. Impact of inverter interfaced distributed generation on overcurrent protection in distribution systems[C]// Power Engineering and Automation Conference. Sept 2011 : 371-376.
  • 10JIN Qiang, LI Yong-li. A study on steady characters of inverter interfaced distributed generation in three phase symmetrical system[C]//International Conference on Power System Technology. Oct. 2010: 1-7.

二级参考文献41

共引文献262

同被引文献41

  • 1吴立杰,陈星莺,徐石明,余昆,马越.考虑电流保护可靠性的分布式电源准入容量研究[J].电网与清洁能源,2015,31(3):35-39. 被引量:13
  • 2王成山,孙晓倩.含分布式电源配电网短路计算的改进方法[J].电力系统自动化,2009,33(12):71-74.
  • 3Q/GDW617-2011.光伏电站接入电网技术规范[S].
  • 4V erband der Netzbetreiber VDN e. v. beim VDEW. Network and system rules of the German transmis- sionsystern operators[ EB/OL]. Berlin, German : VDN, 2007 http ://www.bdew.de/, 2012 - 09 - 23.
  • 5Q/GDW480-2010分布式电源接入电网技术规定[S].北京:中国电力出版社,2010.
  • 6Q/GDW738-2012配电网规划设计技术导则[S].北京:中国电力出版社,2012.
  • 7Hesam Y,Li Yunwei,Wilsun X.A new control strategy to mitigate the impact of inverter-based DGs on protection system[J].IEEE Transactions on Smart Grid,2012,3(3):1427-1436.
  • 8Plet C A,Graovac M,Green T C,et al.Fault response of gridconnected inverter dominated networks[C]//IEEE Power Energy Soc.Gen.Meet.Minneapolis:IEEE,2010:1-8.
  • 9黄伟,雷金勇,夏翔,吴汕,熊军,王函韵,甘德强.分布式电源对配电网相间短路保护的影响[J].电力系统自动化,2008,32(1):93-97. 被引量:88
  • 10雷金勇,黄伟,夏翔,吴汕,熊军,王函韵,甘德强.考虑相间短路影响的分布式电源准入容量计算[J].电力系统自动化,2008,32(3):82-86. 被引量:34

引证文献5