期刊文献+

10kV柱上式高压无功补偿装置有关问题的讨论与建议 被引量:4

Discussion and Suggestion on Some Problems of 10 kV Pole-mounted High Voltage Reactive Power Compensation Device
下载PDF
导出
摘要 文中对装置进行分析后认为:固定接入装置存在因线路自动重合闸而产生高的过电压以及运行中可能出现过补偿等隐患;当采用外熔断器或内熔丝作为电容器内部故障保护时,则分别要求每相电容器并联台数不少于4台或电容器内串联段中需有足够数量的并联元件。据此提出了适当增加并联元件数、提高元件的耐电强度以及增设不平衡保护的建议。 In this paper, it is thought after the analysis of the device that the fixed access device has such hidden dangers as high overvoltage due to reclosing operation of line and over compensation which is pos- sibly occurs during the operation. In case of adopting external fuse or internal fuse wire as internal fault protection of capacitor, the number of parallel connected capacitors for each phase not less than 4 units and sufficient shunt elements in the series connection section inside the capacitor are required respective- ly. Based on this reason the suggestions has been put forward that appropriately increase the number of shunt elements, improve withstand voltage strength of elements and add imbalance protection.
出处 《电力电容器与无功补偿》 2013年第2期5-11,共7页 Power Capacitor & Reactive Power Compensation
关键词 柱上式高压无功补偿装置 电容器组 固定接入装置 熔断器 内熔丝 不平衡保护 pole-mounted high voltage reactive power compensation device capacitor bank fixedaccess device fuse internal fuse imbalance protection