期刊文献+

考虑机网协调的新型发电机失磁保护方案研究 被引量:10

New loss of excitation protection scheme based on coordinated optimization between generator and grid
下载PDF
导出
摘要 随着大型发电机组大量投运,失磁故障对系统的危害日益增大。在厂网分开的背景下,如何同时确保发电机和电网的安全稳定运行是一个值得关注的研究课题。针对发电机失磁保护在系统振荡时容易误动或拒动的问题,研究了失磁和振荡两种情况下系统电气量变化规律的不同特征,并结合不同失磁类型的特点,提出了电压、无功和时间三种新型判据,进而设计了计及机网协调的新型失磁保护方案,并给出了相应动作参数的整定方法。计算机仿真实验表明,新型方案可有效区分失磁和振荡现象,具有动作速度快、可靠性高的优点。 As large capacity units is playing an increasily important role, loss of excitation failure has become more and more dangerous to the power system stability. Especially when the power plants and grid are seperated, it is a main concern to guarantee the security operation of both generators and grid. This paper concentrates on the mal-operation or misoperation problems of loss of excitation protection, which happen frequently in system swings. Based on the different generator performances in the two scenarioes and different kinds of loss of excitation failures, three innovative criterions including voltage, reactive power and timer criterions are proposed. Further, a new loss of excitation protection scheme based on the presented criterions is designed, and the scheme parameters tuning method is also introduced. The computer simulation results show that the new scheme can accurately distinguish the phenomena of loss of excitation from power system swings, and shows the advantages of high action speed and high reliability.
出处 《电力系统保护与控制》 EI CSCD 北大核心 2013年第9期1-6,共6页 Power System Protection and Control
基金 国家高技术研究发展计划(863计划)(2012AA050207) 国家科技支撑计划(2011BAA01B02) 国家自然科学基金(51190101) 国家电网公司科技项目 湖北省电力公司和国电南瑞科技股份有限公司科技项目~~
关键词 失磁保护 系统振荡 电压判据 无功判据 时间判据 机网协调 计算机仿真 loss of excitation protection system swing voltage criterion reactive power criterion timer criterion coordinatedoptimization between generator and grid computer simulation
  • 相关文献

参考文献11

二级参考文献41

共引文献117

同被引文献65

引证文献10

二级引证文献58

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部