期刊文献+

风机盘管来流场均匀化数值模拟 被引量:16

Numerical Simulation of Uniformization of the Head-on Flow Field of the Fan Coil Unit
下载PDF
导出
摘要 通过对单风机风机盘管的来流场进行数值模拟,在风机送风口风速恒定的情况下,优化传统风机盘管结构,研究结果显示,将风机风口置中安排于送风空间有利于提高来流场气流分布均匀性;将送风空间的两侧改为从风机送风口处开始的渐扩风道形式、在送风空间内增加导流片等,均可以不同程度的提高来流场气流分布均匀性,有利于提高风机盘管的换热效率。 The numerical simulation of the Head-on Flow Field of a fan coil unit with a single blower fan was performed. Thestructure of the traditional fan coil unit in the case of the supplied air speed to be constant at the outlet of the fan. The results showed that, the central arrangement of the air outlet of the fan in the supply air space would improve the uniformity of the air distribution in the Head-on Flow Field. The methods of both sides of the supply air space changed as a divergent form starting from the air outlet of the fan, and increased deflectors in the supply air space, could improve the uniformity of the air distribution in the Head-on Flow Field inordinately. This might improve the effect of the heat transmission effectiveness of the fan coil unit.
出处 《流体机械》 CSCD 北大核心 2013年第4期54-57,共4页 Fluid Machinery
基金 天津市自然科学基金(09JCZDJC24900)
关键词 来流场均匀性 风机盘管 送风空间 uniformization of the head-on flow field fan coil air space of flow field
  • 相关文献

参考文献8

二级参考文献25

  • 1兰治科,黄翔,狄育慧.蒸发冷却+干式风机盘管半集中式空调系统探讨[J].西安工程科技学院学报,2006,20(6):735-740. 被引量:21
  • 2殷平.机器露点实验研究(一)──水冷式表冷器机器露点研究[J].通风除尘,1997,16(1):11-14. 被引量:10
  • 3殷平.带独立新风的风机盘管空调系统的设计方法[J].空调设计,1997,(1):11-26.
  • 4宋虎堂,李培宁.蜂窝紧凑结构螺旋板换热器[P].中国专利:200910039599.9,2009-10-08.
  • 5Guide to Compact Heat Exchanger[ EB/OL]. http://www. hw. ac. uk/mecWWW/hexag/CHX.pdf, 2009 - 10 - 12.
  • 6《国务院关于加强节能工作的决定》国发[2006]28号[S].
  • 7江亿.一种基于间接蒸发冷却技术的空调系统[P].中国:ZL200610114684.3,2006-11-21.
  • 8GB50189-2005.公共建筑节能设计标准[S].[S].,2005..
  • 9.采暖通风与空气调节设计规范(GB50019-2003)[S].北京:中国计划出版社,2003..
  • 10杨崇麟 张明石 王中铮.板式换热器工程设计手册[M].北京:机械工业社出版社,1998..