摘要 乐清电厂#2机组运行中,锅炉侧来自不同方向的100多点热电阻温度信号,发生无规律的波动,影响了机组的安全运行。热工专业对DCS系统进行了全面的检查、分析和试验,在未能直接查明和消除干扰源的情况下,通过消除多点接地和对输入信号增加电容滤波的方法,消除了这些温度信号显示值的波动。本文介绍了该问题的查找过程和采用的方法,提出了现场消除或降低干扰的一些简单易行有效的实用措施,供同行参考。 Some irregular fluctuations of the thermal resistance temperature signal which affected the safe operation of the unit took place over 100 points from different direction of the boiler side,during the running of Yueqing power plant #2 unit.The Instrument&Control group checked,analyzed and tested DCS.Since the source of interference could not be identified and eliminated directly,we solved the thermal resistance temperature fluctuations in signal display problems by eliminating Multi-point connection to the ground and installing the capacitance filtering of the input signal.This article introduces the problem of the search process and the method,proposes some simple and effective practical measures to eliminate or reduce the interference.
出处 《仪器仪表用户》 2013年第2期77-79,共3页 Instrumentation
关键词 热电阻 干扰 信号波动 抗干扰措施 thermal resistance interference signal fluctuations anti-jamming measures
  • 相关文献

参考文献3

  • 1DLlT 5190.5-2004电力建设施工及验收技术规范第5部分:热工自动化[S].北京:中国电力出版社2004:29-35,44-45.
  • 2王雁刚.火力发电厂中DCS系统抗干扰措施技术探讨[EBlOL].http://wenku.baidu.comlviewlBlflce8783d049649b6658e7.html,2011-04-20.
  • 3叶国满,屠士凤,林晨,王世云,丁俊宏.抑制信号干扰的方法研究和应用[J].浙江电力,2012,31(12):67-69. 被引量:8