期刊文献+

6kVF-C开关爆炸事故原因分析及处理 被引量:2

Reason analysis and treatment of explosion of 6 kV F-C switch
下载PDF
导出
摘要 针对高压厂用母线的保护配置问题,阐述了1起600 MW发电厂厂用6 kV F-C开关爆炸的事故处理经过及6 kV母线装设快速母线保护的必要性。分析了该厂低电压配电系统继电保护存在的问题,提出了快速母线保护方案。实践验证,采用该方案可避免母线事故对设备造成的损坏。 Aiming at the protection configuration of the busbar for high - voltage power plant, this paper expounds the treatment process of an explosion accident of 6 kV F - C switch for 600 MW power plant and the necessity of rapid busbar protection for 6 kV busbar, as well analyzes the problems in relay protection for the low - voltage distri-bution system in this plant, and proposes the plan to bring in rapid busbar protection. The practice proves that this plan succeeds in avoiding the damage of equipment caused by busbar accidents.
机构地区 华能铜川电厂
出处 《黑龙江电力》 CAS 2013年第2期172-174,177,共4页 Heilongjiang Electric Power
关键词 厂用6 KV母线 F—C开关 爆炸 快速母线保护 级联 弧光保护 6 kV busbar for Electric power plant F - C switch explosion rapid busbar protection cascade arc protection
  • 相关文献

参考文献2

二级参考文献8

共引文献2

同被引文献4

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部