马山智能变电站VFTO对继电保护的影响 被引量:3

The Effect on Relay Protection Device from VFTO of Mashan Smart Substation
下载PDF
导出
摘要 根据辽宁220 kV马山智能变电站的现场测试结果,结合暂态干扰源的特征和智能二次设备采样环节的判据,分析了气体绝缘开关(GIS)设备在倒闸操作时产生的快速暂态过电压(VFTO)对远端采集模块的影响,进而对相关继电保护设备安全性、可靠性的影响,也为GIS远端采集模块采取标准化的屏蔽措施和方案提供了参考依据。 According to the test result of Liaoning 220 kV Mashan smart substation, combining the feature of transient interference source and criterion of smart secondary equipment sampling, it analyses the influence VFTO (Very Fast Transient Overvohage) effects on the remote acquisition module when GIS (Gas Insulated Switchgear) is in switch operation. Futher, the paper discusses the influence on safety and reliability of relay protection devices. It also provides reference for GIS remote acquisition module to select correct shield measure and scheme.
出处 《东北电力技术》 2013年第4期16-20,共5页 Northeast Electric Power Technology
关键词 220 kV马山智能变电站 GIS VFTO 远端采集模块 继电保护设备 220 kV Mashan smart substation GIS VFTO Remote acquisition module Relay protection device
  • 相关文献

参考文献2

二级参考文献16

  • 1Ji Jiaqin(Department of Electrical Engineering).GIS中的VFT过电压分析[J].清华大学学报(自然科学版),1994,34(1):73-82. 被引量:19
  • 2王俊,夏英毅.GIS中的快速暂态过电压现象[J].华通技术,2005,24(2):44-46. 被引量:3
  • 3中国电器工业协会高压开关分会.高压开关设备国内外产品水平[M].北京:机械工业出版社,2000.
  • 4Fujinmoto N,Boggs S A.Characterristics of GIS Disconnector-induced Short Risetime Transients Incident on Externally Connected Power System Components[J] .IEEE Transactions on Power Delivery, 1988, 3(3) :961 - 970.
  • 5华中工学院.上海交通大学.高电压实验技术[M].北京:水利电力出版社,1983.
  • 6Newi G A. High Impedance Nanosecond Risetime Probe for Measuring High Votltage Impulses[J]. IEEE Trasactions on Power Delivery, 1968,9(87):1779- 1786.
  • 7Osmokrovi'c P,Petkovi'c D,Markovi'c O. Measuring Probe for Fast Transiems Monitoring in Gas Insulated Substation[J].IEEE Transactions on Instrumentation and Measrement, 1997,46(1) :36- 44.
  • 8Jayaram S Xu,Cross J D. High Divider Ratio Fast Response Capacitive Dividers for High Voltage Pulse Measurements[J].Thirtieth IAS Annual Meeting IAS' 95, 1995(10) :8- 12.
  • 9史保壮.GIS中快速暂态过电压的测量系统[D].西安:西安交通大学,1997.
  • 10Christian J ,Xie J. Very Fast Transient Oscillation Measurement at Three Gorges Left Bank Hydro Power Plant [j] .2006 International Conference on Power System Technology, 2006:1 - 6.

共引文献11

同被引文献13

  • 1王燕.电流互感器的误差及其对继电保护的影响[J].东北电力技术,2006,27(1):30-33. 被引量:11
  • 2Q/GDW-441-2010,智能变电站继电保护技术规范[S].
  • 3LIU Q, ZHANG Y F. A. Influence of switching conditions on very fast transient over-voltage in 500 kV GIS insulated substation [C]. 2008 International Conference on Electrical Machines and Systems, Xi' an, China., 2008, 17-20, 4451-4454.
  • 4JUAN A, Martinez. Statistics assessment of very fast tran- sient over-voltages in gas insulated substation[C]. Power Engineering Society Summer Meeting, IEEE, 2000, Vol.2 : 882-883.
  • 5MEPPELINK J, DIEDETICH K.J, FESER K, et al. Very fast transients in GIS [J]. IEEE Transactions on Power De- livery, 1989, 4( 1 ):223-233.
  • 6LU T C, ZHANG B. Calculation of Very Fast Transient Over-voltages in GIS [J]. Transmission and Distribution Conference and Exhibition, Asia and Pacific, IEEE/PES, 2005 : 1-5.
  • 7VINOD V K, JOY T M, NAIDU M S. Influence of switch- ing conditions on the VFI'O magnitudes in a GIS [J].IEEE Transactions on Power Delivery, 2001, 16 (4) : 539-544.
  • 8于文斌,杨以涵,郭志忠,周建新.光路结构参数对光学电流互感器运行稳定性的影响[J].电网技术,2008,32(20):68-72. 被引量:10
  • 9陈玥名,崔广泉,刘长江.电力电流互感器检测试验方法研究[J].东北电力技术,2009,30(9):15-17. 被引量:20
  • 10刘盛刚,刘乔,李泽仁.基于全光纤自混合干涉技术的微振动测量研究[J].激光技术,2012,36(1):29-32. 被引量:6

引证文献3

二级引证文献15

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部