期刊文献+

引射器出口背压对满液式蒸发器回油的影响 被引量:1

Effect of ejector outlet back pressure on oil return of flooded evaporator
下载PDF
导出
摘要 压缩机失油是满液式冷水机组常见的问题。通过制作引射器模型并测试引射器出口在不同的背压下引射管的流量值,探讨压缩机失油的成因。测试结果表明:在产品设计或生产中不注意引射器出口背压,是压缩机失油的主要原因之一;在出口处安装弯头、截止阀,会使背压增大,流量减小,甚至出现倒流。因此提出建议:在满液式蒸发器的回油管路中,引射器出口尽量不要使用截止阀、弯头等类似管件;引射管出口管路应水平或向下布置。 Compressor oil shortage is common in flooded chiller. In order to study the reasons of compressor oil shortage,an ejector model is built and the ejecting flow on different ejector outlet back pressure is measured. The test results show that one of the main reasons of compressor oil shortage is incorrect ejector outlet back pressure which is caused in process of design or manufacture,installation of stop valves or elbows after the ejector outlet will make the back pressure increase and ejecting flow decrease, even occur back flow. So some suggestions are proposed: in the oil return pipe line of flooded chiller, it's not to use any pipe fitting such as stop valves,elbows etc. after the ejector outlet as possible,the ejector outlet direction should be horizontal or downward.
作者 刘跃
出处 《制冷与空调》 2013年第3期69-71,共3页 Refrigeration and Air-Conditioning
关键词 满液式冷水机组 满液式蒸发器 压缩机 引射器 回油 flooded chiller flooded evaporator compressor ejector oil return
  • 相关文献

参考文献4

二级参考文献20

  • 1严铭卿.燃气引射器工况研究与优化设计[J].煤气与热力,1994,14(6):20-25. 被引量:8
  • 2丁国良,吴静怡,连之伟,晋欣桥,陈芝久.提高冷水机组能效的技术措施[J].制冷技术,2005,25(2):21-25. 被引量:11
  • 3索科洛夫 黄秋云译.喷射器[M].北京:科学出版社,1977..
  • 4孙厚钧 宋锡铭 等.以流体自控振荡射流促进河道输沙水体增氧与航道浚深.中国水利水电技术进展[M].海洋出版社,1999..
  • 5王时珍.两级吸入式高效高引射系数引射器[J].力学学报,1980,(4).
  • 6索科洛夫EЯ 津格尔HM(著) 黄秋云(译).喷射器[M].北京:科学出版社,1977..
  • 7Keenan H, Neumann E P, Lustwerk F. An investigation of ejector design by analysis and experiment [J]. Appl.Mech. , Trans. ASME, 1950, (72) : 299 - 309.
  • 8Philippe D. A method for visualizing the mixing zone between two coaxial flows in an ejector[J].Optics and Lasers in Engineering, 2001, (35): 317-323.
  • 9Ouzzane M, Aidoun Z. Model development and numerical procedure for detailed ejector analysis and design [J]-Applied Thermal Engineering, 2003, ( 23 ) : 2337 -2351.
  • 10Pridasawas W, Lundqvist P. An energy analysis of a solar-driven ejector refrigeration system [J]. Solar Energy,2004, (76) : 369 - 379.

共引文献68