期刊文献+

悬索桥锚碇大体积混凝土温度控制与施工

Temperature Control and Construction of Anchor Mass Concrete in Cable Suspension Bridge
下载PDF
导出
摘要 黄埔大桥南锚锭底板C30混凝土方量近16 847m3,在取消设置冷却水管通水冷却情况下,通过选择级配优良的碎石、砂、外加剂,掺入矿粉和粉煤灰优化混凝土配合比,控制混凝土的浇筑过程和保温养护,减小水泥用量,降低混凝土的水化温升峰值,提高了混凝土和易性和耐久性.现场实时温度监测表明:锚锭底板未出现温度裂缝,底板最高温度峰值为58.0℃,内表最大温差24.3℃小于规范值25℃,满足工程设计要求. During mass concrete construction of anchors in cable suspension bridge, in order to eliminate tem- perature cracking in concrele, the optimization of concrete mix proportion, reduction of cement quantity,in- crease of mineral aggregate quantity, drop in concrete hydration temperature rise, improvement of pumping construction performance and durability, etc. measures are adopted. The max temperature of anchor floor is 58.0℃; and the max temperature difference of 24.3℃ is less than standard value 25℃. Therefore, the design requirements are satisfied.
作者 汪峰 刘沐宇
出处 《三峡大学学报(自然科学版)》 CAS 2013年第2期61-64,共4页 Journal of China Three Gorges University:Natural Sciences
关键词 悬索桥 大体积混凝土 混凝土配合比 温度控制 锚锭底板 cable suspension bridge mass concrete concrete mix proportion temperature control anchor floor
  • 相关文献

参考文献8

二级参考文献30

共引文献274

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部