摘要
针对高压旁路控制系统采用常规机组控制汽温波动幅度大、控制效果不理想的缺陷,采用600MW超临界机组旁路控制策略。该策略在直流锅炉设置专门的启动旁路系统来排除不合格的工质,在超临界机组启动和低负荷运行期间,在汽轮机负荷(蒸汽流量)达到最小给水流量以前,把蒸汽压力和给水控制延伸到启动旁路系统。通过试验表明,减温阀下游测量汽温的波动为-12℃,改进效果是相当显著的。
To overcome the shortcomings such as large steam temperature fluctuations and unsatisfactory control effects while adopting the conventional unit control in the high-pressure bypass control system, the 600MW supercritical unit bypass control strategy is adopted. A start-bypass system for once-through boiler is specially set in this strategy to exclude the unqualified working fluid; the steam pressure and water control will be extended to the start-bypass system during the startup and low-load operation of the supercritical units, as well as before the turbine load (steam flow) achieves the minimum water flows. Tests have showed that the improved effect is quite remarkable while the downstream measured temperature fluctuation of the temperature reduction valve is -12 ℃
出处
《电站系统工程》
北大核心
2013年第3期57-60,共4页
Power System Engineering
基金
内蒙古自治区自然科学基金(2011MS0721)
内蒙古自治区科技创新引导奖励资金计划(20111603)资助
关键词
超临界
高压旁路系统
600
MW
温度
试验
supercritical
high-pressure bypass system
600MW
temperature
tests