摘要 变电站选址过程中,必须考虑电力系统短路引起的地电位升对邻近市话通信系统的影响。根据我国市话通信系统网络的分布状况和拓朴结构,结合相关行业标准及ITU-T规范,分析了变电站地电位升对其影响的原理,提出了采用相对电位差计算安全间距的方法,并给出了工程计算实例及协调建议。 The short circuit of power system causes the elevation of the ground potential,which will affect the adjacent local communication system.This problem needs to be considered while deciding the location of substation.The principle of the ground potential effects of the urban communicate system is analyzed.According to the distribution and the topology of China local communication system,a method is proposed in this paper to calculate the safe distance based on the potential difference.Other standards such as ITU-T standard are included in this method as well.An engineering case study and coordination suggestions are given in the last part of this work.
机构地区 中南电力设计院
出处 《电力学报》 2013年第2期140-142,共3页 Journal of Electric Power
基金 国家能源局2012年行业标准制(修)订计划(编号 能源20120014)~~
关键词 变电站 市话通信 过电压 安全间距 substation local telecom system overvoltage safe distance
  • 相关文献

参考文献5

  • 1ITU-T Directives-2005. Volume III Capacitive, Inductive and Conductive Coupling: Physical Theory and Calculation Methods[S]. Switzedand Geneva: IUT, 2003.
  • 2邮电部数据通信技术研究所.YDN088-1998自动交换电话(数字)网技术体制[s].北京:人民邮电出版社,1988.
  • 3中华人民共和国信息产业部.YD/T695.2004市话通信系统过电压过电流防护原则及技术要求[s].北京:人民邮电出版社,2004.
  • 4熊万洲.±800 kV直流输电等效干扰电流指标分析[J].电网技术,2008,32(2):81-84. 被引量:8
  • 5Telecommunication Standardization Sector of ITU. ITU-T Recommendation K. 11-2009. Principles of Protection Against Overvoltages and Overcurrents [S]. Switzedand Geneva: IUT, 2003.