Effect of Temperature Differentials on Condensers of Split-Type Air Conditioners in Apartment Buildings

Effect of Temperature Differentials on Condensers of Split-Type Air Conditioners in Apartment Buildings
下载PDF
导出
摘要 Analyzing the effects of heat rejection from condensers of split-type air-conditioning units at lower-floors of MLABs (multi-level apartment buildings), using field measurements to monitor environmental conditions and condenser operation, revealed increases in the inlet air temperature at the condensers at the upper floors, which in turn increased the power and energy requirements for these units and decreased their cooling capacities. Results indicated that a decrease of up to 16,000 tons in cooling capacity and an increase of up to 67.2 MW in the national peak load demand might be reached for a 4 ℃ temperature differential for Kuwait conditions. It is recommended that the condensers be placed in the wind pathway to minimize the impact of heat rejection and stack effect and to optimize the operation of split-type air-conditioning units, and that other factors regarding installation setup and location are investigated.
出处 《Journal of Energy and Power Engineering》 2013年第2期272-276,共5页 能源与动力工程(美国大卫英文)
关键词 Split-type air-conditioning peak load temperature differentials power rating cooling capacity condensers. 空调冷凝器 分体式 公寓楼 温差 散热效果 空调机组 冷却能力 优化操作
  • 相关文献

参考文献8

  • 1M.R. Al-Marafie, R.K. Suri, G.P. Maheshwari, Energy and power management in air-conditioned buildings inKuwait, Energy 14 (9) (1989) 557-562.
  • 2T.T. Chow, Z. Lin, Q.W. Wang, J.W.Z. Lu, Studying thermal performance of split-type air conditioners at building re-entrant via computer simulation, in: The 6th IBPSA International Conference on Building Simulation, Japan, 1999, pp. 1357-1363.
  • 3A. Avara, E. Daneshgar, Optimum placement of condensers of split-type air-conditioners by numerical simulation, Energy and Buildings 40 (2008) 1268-1272.
  • 4C. Chan, T. Lim, Simulation of hot air stack effect in a high-rise condominium, Research and Application Department, Case studies 416, Research and Development Centre, Malaysia, 2007.
  • 5H. Xue, B. Xue, J. Wu, Y. Wei, Prediction of temperature rise near condensing units in "the confined space of a high-rise building, Building and Environment 42 (2007) 2480-2487.
  • 6M. Bojic, S. Savic, D. Nikolic, Application of computational fluid dynamics to flow next to high-rise buildings in Hong Kong due to air-conditioner heat rejection, In. J. Energy Technology and Policy 6 (2008) 159-177.
  • 7G. Wang, Y. Hu, S. Hu, Thermal environment of outdoor units of VRV system in high-rise building, in: Proceedings of Building Simulation, Japan, 2007, pp. 1109-1114.
  • 8H. Xue, S. Chou, X. Zhong, Thermal Environment in a confined space of high-rise building with split air conditioning system, Building and Environment 39 (2004) 817-823.

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部