期刊文献+

燃气轮机加速度保护跳机原因分析与处理 被引量:2

Cause Analysis and Treatment of Gas Turbine Trip Due to Acceleration Protection Action
原文传递
导出
摘要 某联合循环机组加速度保护动作跳机,由于油质化验错误,使得事件原因变得复杂,虽先后进行反馈装置和信号电缆屏蔽接地的可靠性检查、现场抗干扰性能试验、请外方专家现场分析等,但仍未能找到故障原因。后从油路上检查,发现阀门控制油滤网中存在大量软油皮,找到了故障原因,通过更换阀门滤网的方法消除了故障现象。对该故障分析查找过程中的经验与教训进行了总结,提出了跳机故障的防范措施,供专业人员参考。 Because of oil assay error, the trip reason of a combined cycle unit caused by the acceleration protection action is complex. Although, reliability inspection and field anti-interference performance tests were carried out on feedback device and signal cable shielding grounding, as well as foreign experts were invited for on-site analysis, it still failed to find the fault reason. Then, the oil line was checked and the fault reason were found that a large number of soft skins existed in the valve control oil filter. The fault phenomenon was eliminated by replacing the valve's filter. Finally, the experience and lessons of the fault analysis process are summarized tosuggest preventive measures for trip fault, which will provide references for professionals.
出处 《电力建设》 2013年第6期95-97,共3页 Electric Power Construction
关键词 滤网堵塞 干扰 跳闸 燃气轮机 filter plugging interference trip gas turbine
  • 相关文献

参考文献10

二级参考文献18

  • 1孙长生,王建强.浙江省电厂分散控制系统故障原因、处理与建议[J].电力建设,2006,27(2):62-65. 被引量:12
  • 2周晖.9E燃气轮机Mark V(TMR)控制系统故障分析及对策[J].燃气轮机技术,2006,19(4):55-59. 被引量:5
  • 3DL/T774-2004火力发电厂热工自动化系统检修运行维护规程[S].北京:中国电力出版社,2004.
  • 4SDJ 279-90电力建设施工及验收技术规范(热工仪表及控制装置篇)[S].
  • 5孙长生,朱北恒,尹峰,等.火电厂热控系统可靠性配置与事故预控[M].北京:中国电力出版社,2010.
  • 6SPEEDTRONIC^TM Mark V Turbine Control[ z].
  • 7User's Manual[z].GEH-5979D
  • 8Maintenance Manual[z].GEH-5980E
  • 9Application Manual[ z].GEH-6195D
  • 10丁俊宏,苏烨,章卫军,等.提高乐清电厂热控系统可靠性专题报告[R].杭州:浙江省电力试验研究院,2011.

共引文献48

同被引文献16

引证文献2

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部