适用于配电线路无通道保护的备用电源自动投入装置 被引量:4

Automatic switchover device adaptive to distribution line non-communication protection
下载PDF
导出
摘要 根据配电线路无通道保护的特点,设计了新型备自投低压模块的启动判据和动作时间,使非故障失电线路区段的供电恢复时间最大限度减小;在投入到永久性故障再次断开时,备自投的一合一开2次扰动为对侧保护的过电流加速(AOC)模块在加速时间窗内提供电流变化量,可以从电源侧加速切除故障。实时数字仿真实验验证了整套方案的有效性。 According to the characteristics of non-communication protection for distribution line,the startup criterion and operation time of UV(Under Voltage) module are redesigned for a new kind of automatic switchover device to minimize the power recovery time.When the automatic switchover device responds to a permanent fault,two disturbances caused by its close and open operations induce the current variation within the speed-up time window of the AOC(Accelerated Over-Current) module of the protection at opposite side,which accelerates the removal of fault at source side.Real-time digital simulation verifies the effectiveness of the proposed scheme.
出处 《电力自动化设备》 EI CSCD 北大核心 2013年第6期147-151,162,共6页 Electric Power Automation Equipment
基金 国家自然科学基金资助项目(50937003 51007045 51120175001) 北京市自然科学基金资助项目(3102017)~~
关键词 配电线路 无通道保护 备用电源自动投入装置 继电保护 仿真 distribution line non-communication protection automatic switchover device relay protection computer simulation