摘要 论述磁位计的工作原理并通过实验对其可行性进行了验证 ,证明并指出磁位计以其线性好、反应速度快、无磁饱和、体积小、重量轻等特点 ,有可能成为新一代数字化继电保护用电流互感器。 In order to solve the magnetic saturation problem of traditional current transform ers used in protective relaying,a new type of current transformer,that is magnetic potentiom eter,is proposed.Its principle is dissertated from theories and validated by experiments.It is proved out from the results of experim ents that magnetic potentiom eter m ay become the im portant part of new generation of current transform ers for digitalization of protective relaying for its good linearity,fast response,having no magnetic saturation,being sm all in volume and light in weight. This project is supported by the Fund of Excellent Personnel Training Program Across Centuries of National Education Department of China.
出处 《电力系统自动化》 EI CSCD 北大核心 2000年第16期35-38,50,共5页 Automation of Electric Power Systems
基金 国家教育部跨世纪优秀人才培养计划基金 留学回国人员基金资助项目
关键词 磁位计 电流互感器 继电保护 电力系统 magnetic potentiometer hollow core transformer current transform er protective relaying