摘要 针对三相并联逆变器系统同步控制中CAN(controller area network)总线通信方式存在实时性和准确性随总线负载上升而下降和同步相位调节算法存在谐波频率偏移、波形畸变大等问题,该文提出了一种基于CAN总线通信的基准时间同步方法和基于PWM(pulse width modulation)载波周期的相位同步调整算法,采用动态主从同步控制模式,所有逆变器单元依次作为主控单元,按照时间触发和事件触发相结合的方式实时发出包含频率信息的广播同步信号,所有逆变模块据此确定基准时间并调整输出电压的频率和相位使得同相的逆变器输出电压同频率、同相位,而不同相的逆变器输出电压相位互差120°。仿真分析和试验结果表明,该方法使三相并联逆变器系统输出电压各相之间的相位误差和同相之间相位差均在1°之内,可以在无需增加功率器件耐压值和限流值的前提下提高供电系统供电容量。 Three phase grid-connected inverters are the key parts for the transfer of dispersed power generation,such as photovoltaic,wind generation,and energy storage systems,and so on.The three-phase system could be replaced with three single phase inverters.In this way,it could enlarge the current capacity easily without using high isolated voltage and large current devices,and it will be more cheap and flexible.However,there would be a significant frequency offset.With the help of a CAN(Controller Area Network) bus,all the parallel inverters could be the master in the given rules.The master inverter sends the frequency of itself with a synchronization-triggered frame on its clock period,and then all the other inverters determine the frequency of the interval between the two frames.For the other inverters,the frame is also taken as the reference phase,which can correct the phase error of the sine signal.However,the communication data exchange speed and quality fall as the CAN busloads increase.The phase synchronization method will cause frequency offset and voltage distortion.Therefore,a PWM carrier period based parallel inverter synchronization control method based on a CAN bus was proposed in the paper.The method works in dynamic master/slave mode.In the CAN protocol,the pulse width modulation period is selected as the basic communication period.The period is divided into 3 ranges,according to the zero point of ABC phase voltage.Each range is divided into 3 time periods,exclusive,arbitration,and free.In the exclusive time period,the most important message is delivered.In the design of the CAN application layer,the master dynamic setting was implemented on the ID allocation,in which the address is allocated dynamically,and the master is determined.When the system is powered on,or the new one is connected,all the inverters will get this information,and then send the serial numbers and connected phase name to the bus.They can receive the serial numbers and connected phase name of the others later.The master inverters will be decided on the given rule of the serials number.If the master stops sending synchronization signals,the dynamic setting will be repeated again to make the new one.The simulation and experiment of parallel inverters were finished in the carrier period based phase synchronization method.In simulation,the phase change and frequency change methods were adopted to compare with the proposed methods.The reference voltage was set to 220volts,50Hertz,and zero initial phase angles.In the result,the proposed method reduces the voltage distortion from 26.7% to 8.8%,compared to the phase change method,while reducing the frequency offset from 16.67Hertz to 0,compared to the frequency change method.It can be proved from the simulation in Matlab that the method can achieve low distortion and little frequency offset,compared to the other methods.Four inverters were engaged in the experiment,and that is enough to show all the possible capacity enlarging cases with no extra expense.The controller of the inverters was developed on the popular digital processor,which is TMS320F28335 from Texas Instrument.The results show the phase synchronization errors keep within 1° between the inverters in the same phase,or different phases.
出处 《农业工程学报》 EI CAS CSCD 北大核心 2013年第12期179-186,共8页 Transactions of the Chinese Society of Agricultural Engineering
基金 国家高技术研究发展计划(863计划)(2012AA050217)
关键词 分布式发电 同步控制 算法 逆变器并联 CAN总线 distributed power generation synchronization control algorithms parallel inverter CAN bus
  • 相关文献

参考文献29

  • 1Bracale A,Caramia P,Carpinelli G,et al. Site and systemindices for power-quality characterization of distributionnetworks with distributed generation[J]. IEEETransactions on Power Delivery,2011,26(3):1304-1316.
  • 2Kim Jaehyung,Kim Jungu,Ji Younghyok,et al. Anislanding detection method for a grid-connected systembased on the goertzel algorithm[J]. IEEE Transactions onPower Electronics,2011,26(4):1049-1055.
  • 3He Jinwei,Li Yunwei,Munir,M S. A FlexibleHarmonic Control Approach ThroughVoltage-Controlled DG-Grid InterfacingConverters[J]. IEEE Transactions on IndustrialElectronics,2012,59(1):444-455.
  • 4Marei MI,Saadany E F,Salama M M A. A novel controlalgorithm for the DG interface to mitigate power qualityproblems[J]. IEEE Transactions on Power Delivery,2004,19(3):1384-1392.
  • 5Marei M I,Saadany E F,Salama M M A. A flexible DGinterface based on a new RLS algorithm for powerquality improvement[J]. IEEE Systems Journal,20126(1):68-75.
  • 6杜海江,杨明皓,丑丽丽,张泽军.户用风水光直流微电网控制策略与实现[J].农业工程学报,2011,27(8):277-282. 被引量:11
  • 7于蓉蓉,魏学业,覃庆努,吴小进.基于Takagi-Sugeno模糊模型的电流跟踪型光伏并网逆变器[J].农业工程学报,2010,26(5):240-245. 被引量:5
  • 8Soultanis Nikos L,Papathanasiou Stavros A,Hatziargyriou Nikos D. A stability algorithm for thedynamic analysis of inverter dominated unbalanced LVmicrogrids s[J]. IEEE Transactions on Power System,2007,22(1):294-304.
  • 9郑宏,史玉立,孙玉坤,黄健.微电网并网逆变器下垂控制策略的改进[J].农业工程学报,2012,28(6):191-196. 被引量:13
  • 10Arulampalam A,Bames M,Engler A,et al. Control ofpower electronic interfaces in distributed generationMicrogrids[J]. International Journal of Electronics,2004,91(9):503-523.

二级参考文献82

共引文献54

同被引文献52

  • 1王静,张倩,朱晓言,段娜,石钟山,郑永军,王新.基于CAN总线的联合收割机脱粒滚筒测控系统研究[J].农机化研究,2012,34(1):71-75. 被引量:6
  • 2王建彬,杨宜民,陈建平.改进BELVC的四轮驱动机器人运动控制方法[J].华中科技大学学报(自然科学版),2013,41(S1):9-12. 被引量:3
  • 3宫学庚,齐铂金,刘有兵,杨清新,路宗利.电动汽车动力电池模型和SOC估算策略[J].电源技术,2004,28(10):633-636. 被引量:35
  • 4刘明先,裴雪军,侯婷,康勇.全数字化组合式三相逆变器的锁相控制策略[J].电气传动,2007,37(10):39-42. 被引量:6
  • 5Soultanis Nikos L, Papathanasiou Stavros A, Hatziargyriou Nikos D. A stability algorithm for the dynamic analysis of inverter dominated unbalanced LV microgrids[J]. IEEE Transactions on Power System, 2007, 22(1): 294-304.
  • 6Zhang Chunjiang, Chen Guitao, Guo Zhongnan, et al. An Alternating-master-salve Parallel Control Research for Single Phase Paralleled Inverters Based on CAN Bus[C]// Power Electronics and Motion Control Conference, 2006. IPEMC 2006. CES/IEEE 5th International, 2006: 1-5.
  • 7Wang Hongliang, Yue Xiumei, Pei Xuejun, et al. The CAN bus monitor system for the three phase inverters[C]// International Conference on Electrical Machines and Systems, 2009: 1-4.
  • 8Hsieh C C, Hsu P L. The CAN-based synchronized structure for multi-axis motion control systems[C]// 2005 IEEE International Conference on Systems, Man and Cybernetics, 2005: 1314 -1319.
  • 9Min H K, Beom S R, Kyoung C K, et al. Autonomous greenhouse mobile robot driving strategies from system integration perspective: Review and application[C]// Transactions on Mechatronics. America: IEEE/ASME, 2014: 1--12.
  • 10Giovana T T, Eduardo P G, Rubens A T, et al. Hydraulic networked control of four wheel steering agricultural robot [C]//International Conference on Control and Automation. America: IEEE, 2011: 142--147.

引证文献3

二级引证文献43

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部