摘要 以某660MW超临界燃煤海勒式间接空冷机组为例,简化传热系数的计算公式,建立变工况性能计算模型,分析主要因素对凝汽器压力的影响。结果表明:环境温度、凝汽器热负荷越高,凝汽器的压力越大,凝汽器压力随迎风风速的减小呈对数增加规律趋势。所得结论为我国大型海勒式间接空冷机组的优化运行提供理论依据。 HAILLER indirect air-cooled system has the property of saving water and high thermo-economic. Take a 660MW supercritical coalfired unit with HAILLER indirect air-cooled system as an example,the calculation of heat transfer coefficient was simplified,and the off-design model was also built. The main influence parameters for thermo-economics were analyzed. The results show that condenser pressure increases with enhance of environment temperature and condenser heat load. Condenser pressure is logarithmically increased with the decrease of wind speed. The paper provides a theoretical basis for improving the performance of HAILLER indirect air-cooled system.
作者 杨立铭
出处 《节能》 2013年第6期24-27,2,共4页 Energy Conservation
关键词 间接空冷系统 变工况 凝汽器 性能 indirect air-cooled system off-design condenser performance
  • 相关文献

参考文献5

二级参考文献7

  • 1丁尔谋.发电厂空冷技术[M].北京:水利电力出版社,1981..
  • 2尾花英郎 徐中权(译).热交换器设计手册[M].北京:石油工业出版社,1981..
  • 3[4]Van Staden P,Pretorius L,Meyer J P.Simulation of heat exchanger in large air cooled condensers.Heat Transfer 1998,Proceedings of 11 th IHTC,Vol.6 August 23-28,1998,Kyongiu,Korea.
  • 4[5]ACCs strike the right note for Steinway's neightbours.Modern Power Systems.July 2005.
  • 5[1]Swanekamp R.Parallel condensing combines best of all-wet,all -dry methods.Power,JULY/August 1998 ;15 ~ 16.
  • 6杨其国.600MW直接空冷汽轮机技术特点[A].中国电机工程学会,.空冷学术研讨会论文集[C].2001.
  • 7沈红心.水资源的持续开发和利用[J].环境污染与防治,1998,20(3):32-34. 被引量:19