摘要
描述某医药厂房已建冷库与邻室垂直围护结构结露验算方法和测试过程,提出改造方案,实现冷库的防结露改造。并提出结露阴影区的概念及其绘制方法,为分析和解决围护结构内部结露问题提供参考。
Condensation checking calculation method and site test process are described for vertical building enclosure between one cold store and its neighbor room in one pharmaceutical building. Accordingly, the improvement schemes are proposed and reconstruction is finished successfully. At the same time, the definition of condensation shadow area is raised and its drawing method is presented. This is very instructive and useful to analyze and solve the interior condensation problems of building enclosure.
出处
《制冷与空调》
2013年第5期71-75,共5页
Refrigeration and Air-Conditioning
关键词
冷库
围护结构
结露
露点
蒸汽渗透
结露阴影区
cold store
enclosure
condensation
dew point
vapor penetration
condensation shadow area