摘要 对溶液除湿器中传热传质过程进行热力学分析,根据除湿塔的结构及溶液与空气的流动方式,建立除湿器的热质交换物理和数学模型,模拟计算除湿器入口空气和溶液参数对除湿器出口空气参数的影响,得到各入口参数对出口空气温度和含湿量的影响曲线。结果表明:空气出口参数与空气入口含湿量、温度和流量、溶液入口温度和浓度几乎呈线性变化;当溶液入口流量达到2.5 kg/s后,空气出口参数的变化趋于平缓。 The progresses of mass and heat transfer for liquid dehumidifer are analyzed thermodynamically. According to the dehumidification towers size and the flow patterns of liquid and air, the physical and mathematical model of dehumidifier is set up. The effect of the inlet air parameters and inlet liquid parameters on the outlet air is simulated. Each pa- rameter influence curve is obtained by simulation. The results show that outlet air parameters change linearly with the inlet air humidity ratio, temperature and flow, inlet liquid temperature and concentration. When inlet liquid flow is up to 2.5 kg/s, outlet air parameters change relatively smooth.
机构地区 天津商业大学
出处 《制冷与空调》 2013年第5期93-96,61,共5页 Refrigeration and Air-Conditioning
关键词 溶液除湿 除湿器 数值模拟 liquid desiccant dehumidifier numerical simulation
  • 相关文献

参考文献7

二级参考文献20

  • 1徐学利,张立志,朱冬生.液体除湿研究与进展[J].暖通空调,2004,34(7):22-26. 被引量:30
  • 2Factor H M, Grossman G. A packed bed dehumidifier/ regenerator for solar air conditioning with liquid desiccants[J]. Solar Energy, 1980, 24(6): 541- 550.
  • 3Oberg V, Goswami D Y. Experimental study of the heat and mass transfer in a packed bed liquid desiccant air dehumidifier [J]. Journal of Solar Energy Engineering, 1998, 120(4) : 289 - 297.
  • 4Fumo N, Goswami D Y. Study of an aqueous lithium chloride desiccant system: air dehumidification and desiccant regeneration[J]. Solar Energy, 2002, 72(4): 351 - 361.
  • 5Sultan G I, Hamed A M, Sultan A A. The effect of inlet parameters on the performance of packed tower regenerator[J]. Renewable Energy, 2002, 26(2): 271-283.
  • 6Ali A, Vafai K. An investigation of heat and mass trans-fer between air and desiccant film in an inclined parallel and counter flow channels [ J ]. International Journal of Heat and Mass Transfer, 2004, 47(8) : 1745 - 1760.
  • 7Gandhidasan P, Ullah U R, Kettleborough C F. Analysis of heat and mass transfer between a desiccant-air system in a packed tower[J]. Journal of Solar Energy Engineering, 1987, 109(5): 89-93.
  • 8Khan A Y. Parametric analysis of heat and mass transfer performance of a packed-type liquid desiccant absorber at part-load operation conditions [ J ]. ASHRAE Transactions, 1996, 102(1): 349-357.
  • 9Ren Chengqin, Jiang Yi, Zhang Yianpin. Simplified analysis of coupled heat and mass transfer processes in packed bed liquid desiccant-air contact system [ J ]. Solar Energy, 2006, 80(1): 121-131.
  • 10Ren Chengqin. Corrections to the simple effectiveness- NTU method for counterflow cooling towers and packed bed liquid desiccant-air contact systems[J ]. International Journal of Heat and Mass Transfer, 2008, 51(1 -2): 237 - 245.