摘要
分析滨州、东营沿海地区风电发展现状,对滨州电网沾化电厂供电区域发供平衡潮流进行分析,提出在董堂站安装220 kV滨董线过流联切风电机组装置的稳控方案,使沾化电厂供电区域的220 kV线路一回线路掉闸另一回线路出现过负荷的情况得到有效控制。
Through the analysis of the status of wind power development of the coastal areas in Binzhou and Dongying area, the balance of power flow in Zhanhua power plant area on Binzhou power grid, proposed the stability control scheme of installing 220 kV Bindong line overcurrent intertripping wind power unit in Dongtang station, effectively controlled the situation of another line may overload with one of the 220 kV line circuit switching off.
出处
《山东电力技术》
2013年第4期36-38,共3页
Shandong Electric Power
关键词
风电
过流
联切
稳控
1wind power
over current
intertripping
stability control