期刊文献+

220kV双母线倒闸操作危险点分析及预控措施 被引量:4

Analysis and precaution control measure on dangerous point of 220 kV double bus bars reversal switch operation
下载PDF
导出
摘要 随着宁夏电网变电站综合自动化改造工作的展开,220 kV双母线倒闸操作越来越频繁。通过对母线倒闸操作中母联断路器控制电源和母线隔离开关操作顺序的选择、母线隔离开关辅助触点接触不良或未接触的成因分析,提出母线倒闸操作危险点预控措施。应用结果表明:母线倒闸操作危险点分析有助于提升运行人员标准化倒闸操作水平,防止误操作事故的发生。 With the substation integrated automation improvement developing in Ningxia power grid,220 kV double bus bars reversal switch operation will be more and more frequently.Through the selection of switch operating sequence of bus bars connection circuit breaker control power source and bus bars isolating switch in the bus bars reversal switch operation,and the analysis of dangerous points bringing causes of poor contact or no contact on the auxiliary contact of bus bars isolating switch,puts forward precaution and control measure for the dangerous points in bus bars reversal switch operation.The application result shows that dangerous point analysis in bus bars reversal switch operation is helpful to improve operators’standardization switching operation level and prevent misoperation hap pening.
作者 张颖
出处 《宁夏电力》 2013年第3期30-33,共4页 Ningxia Electric Power
关键词 双母线 倒闸操作 危险点 预控措施 double bus bars reversal switch operation dangerous point precaution measure
  • 相关文献

参考文献2

  • 1钱振华.电气设备倒闸操作技术问答第2版[M].北京:中国电力出版社,2002.
  • 2国家电网公司.生产技能人员职业能力培训专用教材变电运行(220kV)(下)[M].北京:中国电力出版社.2010.