上海地区间歇式空调建筑夜间通风降温策略 被引量:12

Night ventilation strategy applied to intermittent air conditioning buildings in Shanghai
下载PDF
导出
摘要 以上海地区典型办公建筑为例,分析了换气次数、室内热源、通风温差控制模式、楼层及朝向对夜间通风降温节能效果的影响。结果显示,保证5~10h-1换气次数的有效夜间通风,可以实现较好的降温冷却效果;夜间通风能够显著地减小室内热源对空调开机负荷的影响,可以基本消除夜间室内15~25W/m2的内部热扰量;根据室内外温差进行通风控制,可以在室内热源发热量较小的情况下提高节能效果;房间负荷越大,通风节能效果越好。 Taking a typical office building in Shanghai as an example,analyses the influences of air changes,indoor heat sources,ventilation temperature difference control mode,floor and orientation on cooling and energy saving effects of night ventilation.The results show that a better cooling effect can be achieved if the air changes of 5 to 10 h^-1 can be reached.The night ventilation can reduce significantly the influence of indoor heat sources on the opening load of air conditioning,and remove the indoor heat gain of 15 to 25 W/m^2.Night ventilation could further increase energy savings if the temperature control modes are optimized when the total heat gains is at the low level.The heavier the indoor cooling load,the better energy saving effect of the night ventilation is.
作者 李峥嵘 曹斌
出处 《暖通空调》 北大核心 2013年第7期73-77,共5页 Heating Ventilating & Air Conditioning
关键词 夜间通风 降温 节能 换气次数 室内热源 通风温差控制 night ventilation cooling energy saving air changes indoor heat source ventilation temperature difference control
  • 相关文献

参考文献12

  • 1Frank T.Climate change impacts on building heating andcooling energy demand in Switzerland[J].Energy andBuildings,2005,37(11):1175-1185.
  • 2Geros V,Santamouris M.Experimental evaluation of nightventilation phenomena[J].Energy and Buildings,1999,29(2):141-154.
  • 3Finn D P,Connolly D,Kenny P.Sensitivity analysis of amaritime located night ventilated library building[J].SolarEnergy,2007,81(6):697-710.
  • 4Artmann N,Manz H,Heiselberg P.Parameter study onperformance of building cooling by night-time ventilation[J].Renewable Energy,2008,33(12):2589-2598.
  • 5Blondeau P,Allard F.Night ventilation for building coolingin summer[J].Solar Energy,1997,61(5):327-335.
  • 6Kolokotroni M,Aronis A.Cooling-energy reduction in air-conditioned offices by using night ventilation[J].AppliedEnergy,1999,63(4):241-253.
  • 7Wu Lixia,Zhao Jianing,Wang Zhaojun.Night ventilationand active cooling coupled operation for large supermarkets incold climates[J].Energy and Buildings,2006,38(12):1409-1416.
  • 8曹叔维,李峥嵘.晚间通风的计算及其与机械供冷的关系[J].建筑热能通风空调,1999,18(3):12-15. 被引量:4
  • 9李峥嵘,陈沛霖,裴晓梅.晚间通风房间热环境的改善[J].建筑热能通风空调,2001,20(3):27-28. 被引量:16
  • 10Breesch H,Bossaer A,Janssens A.Passive cooling in a low-energy office building[J].Solar Energy,2005,79(6):682-696.

二级参考文献9

  • 1燕达,谢晓娜,宋芳婷,江亿.建筑环境设计模拟分析软件DeST 第一讲 建筑模拟技术与DeST发展简介[J].暖通空调,2004,34(7):48-56. 被引量:141
  • 2李峥嵘.蒸发冷却技术与相变技术在晚间通风中的应用研究.博士学位论文[J].-,1997,.
  • 3李峥嵘.蒸发冷却技术与相变技术在晚间通风系统中的应用研究:博士学位论文[M].同济大学,1997..
  • 4裴晓梅.晚间通风与居室热环境:硕士学位论文[M].同济大学,1995..
  • 5OEROS V, SANTAMOURIS M, KARATASOU S, et al. On the cooling potential of night ventilation techniques in the urban environment[J]. Energy and Buildings, 2005,37:243-257.
  • 6GIVONI Baruch. Effectiveness of mass and night ventilation in lowering the indoor daytime temperatures-Part Ⅰ:1993 experimental periods[J]. Energy and Buildings, 1998,28:25-35.
  • 7KOLOKOTRONI M, WEBB B C, HAYES S D. Summer cooling with night ventilation for office buildings in moderate elimates[J]. Energy and buildings,1998,27(3):231-237.
  • 8KOLOKOTRONI M, ARONIS Aj. Cooling-energy reduction in air -conditioned offices by using night ventilation[J]. Applied Energy, 1999,63(4):241-253.
  • 9刘艳峰,刘加平.建筑外壁面换热系数分析[J].西安建筑科技大学学报(自然科学版),2008,40(3):407-412. 被引量:34

共引文献21

同被引文献76

引证文献12

二级引证文献43

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部