期刊文献+

双馈风力发电机网侧变流器新型拓扑控制研究

Study on a new topology for grid side converter control of doubly-fed wind power generation system
下载PDF
导出
摘要 文章对大功率双馈风力发电机网侧变流器并网时,电压不平衡问题提出一种有效网侧控制拓扑结构,该结构采用3个单相变流器代替原有的三相变流器,通过补偿电压达到限制故障电流同时稳定直流电压的目的。本方法减小了变流器容量,增强了可控性和适应性,同时还可在电压跌落或波动情况下保持同步到电网。最后在MATLAB/SIMULINK环境下,验证了文章所提控制方案的有效性。 In this paper, a problem of grid side converter for large power doubly fed induction generatorsis studied, and a comprehensive analysis of the mathematical model for wind turbine is carried out. For the grid voltage unbalance issues, an effective grid-side control strategy is proposed. The strategy has a topology with three single-phase converters instead of one three-phase converter, voltage is in- jected into the transmission line in series to limit the fault currents as well as to balance the voltages. The method reduces the inverter capacity, enhances its controllability and adaptability. This scheme can synchronize wind turbines and grid during faults or during voltage sags and swings. Finally, The ef- fectiveness of the proposed control strategy is confirmed with simulation results in MATLAB/ SIMULINK environment.
出处 《可再生能源》 CAS 北大核心 2013年第9期35-38,43,共5页 Renewable Energy Resources
基金 辽宁省教育厅项目资助(L2012463)
关键词 双馈风力发电机 单项变流器 限制故障电流 电压不平衡补偿 DFIG single phase converter limit fault current voltage unbalance compensation
  • 相关文献

参考文献12

  • 1DAWEI ZHI,LIE XU,BARRY W WILLIAMS. Model- based predictive direct power control of doubly fed in- duction generator[J]. IEEE Trans on Power Electron- ics.2010,25 (2) : 341-351.
  • 2SINGH, B EMMOJI,V SINGH,et al. Performance e- valuation of new series connected grid-side converter of doubly-fed induction generator [A].Power System Technology and IEEE Power India Conference[C]. India : IEEE, 2008,1-8.
  • 3李学哲,黄成玉,张全柱,邓永红.MW级大功率风电机组变流器系统的研究[J].电气技术,2011,12(5):21-24. 被引量:1
  • 4ABDEL BAQI O,NASIRI A. A dynamic LVRT solution for doubly fed induction generators [J].IEEE Transac- tions on Power Electronics, 2010,25 ( 1 ) : 193-196.
  • 5国家电网公司.Q/GDW392-2009风电场接人电网技术规定[S].
  • 6CHRISTIAN WESSELS.Dynamic voltage restorer to al- low LVRT for a DF1G wind turbine[A].Industrial Elec- tronics[Cl.Bari : ISLE, 2010,803-808.
  • 7ABDEL BAQIO,NASIRIA.A dynamic LVRT solution for doubly fed induction generators [J].IEEE Trans on Power Electronics, 2010,25 ( 1 ) : 193-196.
  • 8黎芹,张兴,杨淑英,谢震.双馈风力发电机低电压穿越转子动态过程分析[J].电力系统及其自动化学报,2010,22(5):19-24. 被引量:19
  • 9GUO JIAHU,ZHANG LUHUA,CAI XU.Dynamie re- sponse of wind power generation based on DFIG under grid fault [A].Proeeedings of IEEE the 6th Interna- tional Power Electronics and Motion Control Con- ferenee[C].Wuhan : IEEE, 2009,2275-2278.
  • 10SERPA L A,PONNALURI S,BARBOSA P METAL. A Modified direct power control strategy allowing the Con- nection of three-phase inverters to the grid through LCL fihers[J].IEEE Transactions on Industry Appli- cations, 2007,43 (5) : 1388-1400.

二级参考文献14

  • 1杨俊华,吴捷,杨金明,杨苹.现代控制技术在风能转换系统中的应用[J].太阳能学报,2004,25(4):530-541. 被引量:16
  • 2Thiringer T, Petersson A, Petru T. Grid disturbance response of wind turbines equipped with induction generator and doubly-fed induction generator[C]// IEEE Power Engineering Society General Meeting, Toronto, Canada.. 2003.
  • 3Lopez J, Sanchis P, Roboam X, et al . Dynamic behavior of the doubly fed induction generator during three-phase voltage dips[J]. IEEE Trans on Energy Conversion, 2007,22(3) : 709- 717.
  • 4He Yikang, Hu Jiabing, Zhao Rende. Modeling and control of wind-turbine used DFIG under network fault conditions[C] // Eighth International Conference on Electrical Machines and Systems, Nanjing, China: 2005.
  • 5Morren J, de Hann S W H. Short-circuit current of wind turbines with doubly fed induction generator [J]. IEEE Trans on Energy Conversion, 2007,22( 1 ) : 174-180.
  • 6Vicatos M S, Tegopoulos J A. Transient state analysis of doubly-fed induction generator under three phase short circuit[J]. IEEE Trans on Energy Conversion, 1991, 6(1):62-68.
  • 7IEEE P1547. IEEE standard for distributed resources interconnection with electric power systems[S].
  • 8Xiang Dawei, Ran Li, Tavner P J, et al . Control of a doubly fed induction generator in a wind turbine during grid fault ride-through[J]. IEEE Trans on Energy Conversion, 2006,21(3) :652-662.
  • 9Petersson A. Analysis, Modeling and Control of Doubly-fed Induction Generators for Wind Turbines [D]. Goteborg, Sweden: Department of Energy and Environment, Chalmers University of Technology, 2005.
  • 10Abbey C, Wei Li , Owatta L, et al . Power electronic converter control techniques for improved low voltage ride through performance in WTGs[C]//37th IEEE Power Electronics Specialists Conference, Jeju, Korea: 2006.

共引文献18

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部