期刊文献+

Insulation Diagnosis of Service Aged XLPE Power Cables Using Statistical Analysis and Fuzzy Inference 被引量:1

Insulation Diagnosis of Service Aged XLPE Power Cables Using Statistical Analysis and Fuzzy Inference
下载PDF
导出
摘要 Cables that have been in service for over 20 years in Shanghai, a city with abundant surface water, failed more frequently and induced different cable accidents. This necessitates researches on the insulation aging state of cables working in special circumstances. We performed multi-parameter tests with samples from about 300 cable lines in Shanghai. The tests included water tree investigation, tensile test, dielectric spectroscopy test, thermogravimetric analysis (TGA), fourier transform infrared spectroscopy (FTIR), and electrical aging test. Then, we carried out regression analysis between every two test parameters. Moreover, through two-sample t-Test and analysis of va- riance (ANOVA) of each test parameter, we analyzed the influences of cable-laying method and sampling section on the degradation of cable insulation respectively. Furthermore, the test parameters which have strong correlation in the regression analysis or significant differ- ences in the t-Test or ANOVA analysis were determined to be the ones identifying the XLPE cable insulation aging state. The thresholds for distinguishing insulation aging states had been also obtained with the aid of statistical analysis and fuzzy clustering. Based on the fuzzy in- ference, we established a cable insulation aging diagnosis model using the intensity transfer method. The results of regression analysis indicate that the degradation of cable insulation accelerates as the degree of in-service aging increases. This validates the rule that the in- crease of microscopic imperfections in solid material enhances the dielectric breakdown strength. The results of the two-sample t-Test and the ANOVA indicate that the direct-buried cables are more sensitive to insulation degradation than duct cables. This confirms that the tensile strength and breakdown strength are reliable functional parameters in cable insulation evaluations. A case study further indicates that the proposed diagnosis model based on the fuzzy inference can reflect the comprehensive aging state of cable insulation well, and that the cable service time has no correlation with the insulation aging state. Cables that have been in service for over 20 years in Shanghai, a city with abundant surface water, failed more frequently and induced different cable accidents. This necessitates researches on the insulation aging state of cables working in special circumstances. We performed multi-parameter tests with samples from about 300 cable lines in Shanghai. The tests included water tree investigation, tensile test, dielectric spectroscopy test, thermogravimetric analysis (TGA), fourier transform infrared spectroscopy (FTIR), and electrical aging test. Then, we carried out regression analysis between every two test parameters. Moreover, through two-sample t-Test and analysis of va- riance (ANOVA) of each test parameter, we analyzed the influences of cable-laying method and sampling section on the degradation of cable insulation respectively. Furthermore, the test parameters which have strong correlation in the regression analysis or significant differ- ences in the t-Test or ANOVA analysis were determined to be the ones identifying the XLPE cable insulation aging state. The thresholds for distinguishing insulation aging states had been also obtained with the aid of statistical analysis and fuzzy clustering. Based on the fuzzy in- ference, we established a cable insulation aging diagnosis model using the intensity transfer method. The results of regression analysis indicate that the degradation of cable insulation accelerates as the degree of in-service aging increases. This validates the rule that the in- crease of microscopic imperfections in solid material enhances the dielectric breakdown strength. The results of the two-sample t-Test and the ANOVA indicate that the direct-buffed cables are more sensitive to insulation degradation than duct cables. This confirms that the tensile strength and breakdown strength are reliable functional parameters in cable insulation evaluations. A case study further indicates that the proposed diagnosis model based on the fuzzy inference can reflect the comprehensive aging state of cable insulation well, and that the cable service time has no correlation with the insulation aging state.
出处 《高电压技术》 EI CAS CSCD 北大核心 2013年第8期1932-1940,共9页 High Voltage Engineering
基金 Project supported by National Natural Science Foundation of China(51277117), Shang- hai Science and Technology Comrmssion(11 DZ2283000).
关键词 交联聚乙烯绝缘电力电缆 模糊推理 统计分析 诊断服务 傅立叶变换红外光谱 电缆绝缘层 老化状态 电击穿强度 XLPE cable in-service aging multi-parameter tests insulation diagnosis statistical analysis fuzzy clustering
  • 相关文献

参考文献11

二级参考文献219

共引文献367

同被引文献25

  • 1Maruyama A, Komori F, Suzuoki Y, et al. High temperature PD de- gradation characteristics in bulk and interfaces of insulating materials for power cables[C]//2000 IEEE International Conference on Proper- ties and Applications of Dielectric Materials. Xi'an, China: IEEE, 2000: 264-267.
  • 2Dalai S B, Gorur R S, Dyer M L. Quantifying degradation of XLPE insulated distribution cables[C]//2004 IEEE Power Engineering So- ciety General Meeting. Denver, USA: IEEE, 2004: 1841-1845.
  • 3Scarpa P C N, Bulinski A T, Bamji S, et al. Dielectric spectroscopy measurements on polyethylene aged in AC fields in dry and humid en- vironments[C]// 1994 IEEE Annual Report Conference on Electrical Insulation and Dielectric Phenomena. Arlington, USA: IEEE, 1994: 437-444.
  • 4Ross R, Geurts W S M, Smit J J. FTIR microspectroscopy and dielec- tric analysis of watertrees in XLPE[C] //1988 Fifth International Conference on Dielectric Materials, Measurements and Applications. Canterbury, New Zealand: IET, 1988: 313-317.
  • 5Stone G C. The statistics of aging models and practical reality[J]. IEEE Transactions on Electrical Insulation, 1993, 28(5): 716-728.
  • 6Fothergill J C, Montanari G C, Stevens G C, et al. Electrical, micro- structural, physical and chemical characterization of HV XLPE cablepeelings for an electrical aging diagnostic data base[J]. IEEE Transac- tions on Dielectrics and Electrical Insulation, 2003, 10(3): 514-527.
  • 7Kobayashi K, Nakayama S, Niwa T. A new estimation method of thermal history in crosslinked polyethylene[C]//1994 IEEE Interna- tional Conference on Properties and Applications of Dielectric Materials. Brisbane, Australia: IEEE, 1994: 678-681.
  • 8GUO Qian. Thermal aging test and life evaluation of low voltage XLPE cable[J]. Electric Wire & Cable, 1999(2): 42-43.
  • 9杜伯学,马宗乐,高宇,程欣欣,杨林,李宏博.采用温差法的10kV交联聚乙烯电缆水树老化评估[J].高电压技术,2011,37(1):143-149. 被引量:22
  • 10王黎明,侯经洲,陈昌龙.用电磁波速诊断XLPE电缆绝缘[J].高电压技术,2011,37(12):2984-2989. 被引量:14

引证文献1

二级引证文献7

相关作者