电力变压器排油充氮装置误动原因分析及对策 被引量:1

Cause Analysis of Power Transformer Oil Discharge Nitrogen Charging Device Misoperation and Countermeasures
下载PDF
导出
摘要 油浸式电力变压器大量使用排油充氮装置作为其消防设备,排油充氮装置的安全性直接影响到变压器运行的安全。针对某变电站1号主变压器排油充氮装置动作、主变压器器保护动作,现场试验检查发现,事故发生时,距离主变压器约30 m处有施工现场夯实场地,压路机作业振动较大,由于振动导致排油重锤跌落是事故直接原因。对此提出多条有关合理使用排油充氮装置及防止其误动的建议和对策。 Oil-immersed power transformer use the oil discharge nitrogen charging device extensively as the fire fighting equipment. The safety of the oil discharge nitrogen charging device directly affects the safety of transformer running. For the oil discharge nitrogen charging device of the main transformer 1 in some substation action, the main transformer protection action, on-site test inspection turned out that some construction site was compacting the field within 30 m from the main transformer, the distance of the main transformer within 30 m compaction site on the construction site, and the vibration of the roller is higher, resulted in oil discharge hammer dropping. Put forward some suggestions about the rational use of oil discharge nitrogen charging device to prevent the misoperation.
出处 《内蒙古电力技术》 2013年第4期76-78,82,共4页 Inner Mongolia Electric Power
关键词 油浸式电力变压器 排油充氮装置 排油重锤 误动作 oil-immersed power transformers oil discharge nitrogen charging device oil discharge heavy hammer misoperation
  • 相关文献

参考文献3

共引文献9

同被引文献5

  • 1吕向明,安治贤,冯晓东.主变压器冷却装置控制方式的改进[J].内蒙古电力技术,2005,23(6):32-33. 被引量:2
  • 2中国电力科学研究院.GB/T 7252-2001变压器油中溶解气体分析判断导则[S] .北京:中国标准出版社,2001.
  • 3电力行业电力变压器标准化委员会.DL/T 572-2010电力变压器运行规程[S] .北京:中国电力出版社,2010.
  • 4中华人民共和国电力工业部安全监察及生产协调司,国家电力调度通信中心.DL/T 596-1996电力设备预防性试验规程[S] .北京:中国电力出版社,1996.
  • 5电力行业高电压试验技术标准化委员会.DL/T 417-2006电力设备预防性试验规程[S] .北京:中国电力出版社,2006.

引证文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部