期刊文献+

松潘某酒店暖通设计

HVAC Design for a Songpan Hotel
下载PDF
导出
摘要 松潘某酒店建筑总建筑面积7647.1m2,共12层,总建筑高度46.2m。根据气候特点,只考虑冬季供暖,夏季无需空调。4-12层为客房区,采用风机盘管+新风系统,每层设独立新风系统。1-4层健身房、KTV以及后勤用房等采用吊顶空气处理器+新风系统;每层设两个新、排风系统。热源采用两台真空锅炉。空调水系统为一次泵两管制变流量系统,并采用膨胀水箱定压补水。4-12层内走道、健身房和KTV设排烟系统。楼梯间与前室设正压送风系统。 The HVAC systems are designed for a hotel in Songpan, which has a total building area of 7647.1 m^2, 12 floors and a height of 46.2 m. In this design only consider is heating in winter according to the climatic characteristics. Primary air fan-coil systems are employed in guest room areas (the 4th floor to the 12th floor), with a primary air system for each floor. Ceiling mounted air-handle-units are used in lager spaces such as the gym, KTV (lSt-4th floor); in the lSt-4th floor two primary air systems and exhaust ventilation systems are designed respectively. Two vacuum gas/oil boilers are used. A variable-primary-flow two-pipe water system is selected with an expansion tank on the roof. Smoke extraction systems and positive pressure mechanical air supply systems are designed according to national codes.
出处 《制冷与空调(四川)》 2013年第4期348-351,共4页 Refrigeration and Air Conditioning
关键词 酒店 供暖 风机盘管+新风系统 空气处理器 水系统 排烟系统 hotel heating primary air fan-coil system air-handle-unit water system smoke extraction system
  • 相关文献

参考文献8

  • 1GB50189-2005公共建筑节能设计标准[S].北京:中国建筑工业出版社,2005.
  • 2刘涛,苏华.宁城地质博物馆空调和防排烟设计[J].制冷与空调(四川),2010,24(2):41-44. 被引量:1
  • 3路越.某寒冷地区博物馆空调设计实例[J].制冷与空调(四川),2010,24(4):92-94. 被引量:2
  • 4陆耀庆.实用供热通风设计手册[M].北京:中国建筑工业出版社,2008.
  • 5GB50019-2003采暖通风与空气调节设计规范[S].北京:中国计划出版社,2003.
  • 6GB50016—2006建筑设计防火规范[S].北京:中国计划出版社,2006.
  • 7GB50045—95,高层民用建筑设计防火规范[S].北京:中国计划出版社.2005.
  • 807K103-1,防排烟及暖通空调防火设计[S].北京:中国建筑工业出版社,2007.

二级参考文献5

共引文献211

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部