Ⅰ级洁净手术室下限截面风速的试验研究——《医院洁净手术部建筑技术规范》修订组研讨系列课题之八 被引量:5

Experimental study on the lowest requirement of air velocity at operation height for class I operation room:Part 8 of the series of research practice of the revision task group of the Architectural technical code for hospital clean operating department
下载PDF
导出
摘要 洁净手术室通风空调系统的运行能耗在医院运行能耗中占有相当大的比例。以实地对比试验研究为手段,对I级洁净手术室截面风速限值是否存在下调空间进行比较研究。试验结果表明,手术室截面风速下调至0.22m/s后,虽然导致动态条件下手术区浮游菌浓度上升,但从术中感染控制的角度来看,上升幅度仍处于可控制、可接受的范围内。 Energy consumption of HVAC systems for clean operation rooms contributes a considerable part of the total energy consumed by a hospital. Performs an experimental case study in a class 1 operation room to investigate the possibility of reducing the servicing airflow rate of the HVAC system. The results show that although the airborne microorganism concentration rises as the air velocity at the operation height reduced to 0.22 m/s, the surgery site infection risk is still controllable and acceptable.
出处 《暖通空调》 北大核心 2013年第9期48-52,共5页 Heating Ventilating & Air Conditioning
关键词 洁净手术室 术中感染控制 能耗 风速限值 通风空调系统 clean operation room, surgery site infection control, energy consumption, limitation ofairflow rate, ventilation and air conditioning system
  • 相关文献

参考文献3

  • 1中国卫生经济学会医疗卫生建筑专业委员会.GB50333-2002医院洁净手术部建筑技术规范[S].北京:中国计划出版社,2002
  • 2武迎宏,邱侠,王守军.医院洁净手术间不同时段空气质量监测结果分析[J].中华医院感染学杂志,2010,20(20):3155-3157. 被引量:7
  • 3北京市医院感染管理质量控制和改进中心.DB11/408--2007医院洁净手术部污染控制规范[s].北京:北京市质量技术监督局,2007.

二级参考文献4

  • 1涂光备,涂有.对当前医院手术室建设中一些问题的思考[J].暖通空调,2007,37(1):43-47. 被引量:7
  • 2中华人民共和国建设部,中华人民共和国国家质量监督检验检疫总局.GB50333-2002医院洁净手术部建筑技术规范[S].中国计划出版社,2002.
  • 3GB15982-1995.医院消毒卫生标准[S].[S].国家技术监督局 卫生部,1996-3..
  • 4北京市质量技术监督局.医院洁净手术部污染控制规范[S].DB11/408-2007.北京:2007.

共引文献26

同被引文献44

引证文献5

二级引证文献23

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部