摘要 不凝气体(NCG)是影响热虹吸环路稳态热性能的重要因素。本文向热虹吸环路内主动充装氮气模拟实际的不凝气体,获得了不凝气体含量、加热功率、热沉形式等参数对于系统稳态运行特性的影响。实验结果表明,NCG提高了蒸发器温度,进而改变整个系统的温度分布。随NCG含量增加,总热导降低,系统的传热和散热能力随之下降。NCG对工作性能的影响在低温下更加显著。 Non-condensable gas (NCG) is one of the main causes affecting the steady-state operating char- acteristics of the loop thermosyphon. Nitrogen was injected into the loop thermosyphon as NCG, and the steady-state operating characteristics of the loop thermosyphon with NCG was systematically studied for different NCG inventories, heat loads applied to the evaporator, and heat sink conditions. Experimental re- sults reveal that NCG elevates the operating temperature of the evaporator. The more NCG exists, the lower the total thermal conductance thus the heat transfer capability of the loop thermosyphon. Moreover, the ef- fect of the NCG was pronounced at the low temperature region
作者 何江 林贵平
出处 《电子测试》 2013年第9期4-7,共4页 Electronic Test
关键词 热虹吸环路 不凝气体 温度分布 热导 loop thermosyphon, non-condensable gas temperature distribution thermal conductance
  • 相关文献

参考文献10

  • 1Alessandro, Franco: Sauro F., 2011, "Closed Loop Two-Phase Thermosyphon of Small Dimensions: a Revie of the Experimental Results," MICROGRAVITY SCIENCE AND TECHNOLOGY, DOI: 10.1007/s12217-011- 9281-6.
  • 2Kang, Y. H., Kang, M. C., and Chun, W. G., 2003,"A Study Collector Int. Comm. on Thermal Characteristics of the Solar Made with a Closed Loop Thermosyphon, " Heat Mass Transfer, 30(7), pp. 955-964.
  • 3Bo, Z., Yu, S., Ji, C., and Jing L., 2011, "In- situ Test Study on the Cooling Effect of Two- Phase Closed Thermosyphon in Marshy Permafrost Regions along the Chaidaer-Muli Railway, Qinghai Province, China," Cold Regions Science and Technology, 65, pp. 456-464.
  • 4Piyush, S., Mike, P. 2010, "Phase Change Vivek, U., an Heat Transfer Process Heat Applications," Nuclear and Design, 240, 2409-2414 d Fred, G., Device for Engineering.
  • 5McGlen, R. J., Jachuck, R., and Lin, S., 2004 "Integrated High Power Engineering, Thermal Management Electric Devices," 24, pp. 1143-1156 Techniques for Applied Thermal.
  • 6Tu, C. J., Wang, and C. Y., 1988, "Noncondensable Gas Effect on Condensation in a Separate Type Two- Phase Closed Thermosyphon," Heat Mass Transfer, 23(3), pp. 153-158.
  • 7Mantelli, M. H., Angelo, W. B., and Borges, T, 2010, Performance of Naphthalene Thermosyphons with Non-Condensable Gases - Theoretical Study and Comparison with Data," International JournaI of Heat and Mass Transfer, 53, pp. 3414-3428.
  • 8Richter, R., 1990, "Evolution of Non-Condensable Gas in Ammonia Heat Pipes," AIAA Paper No. 90-1757.
  • 9Randeep, S., Aliakbar, A., and Masataka, M., 2010, "Operational Characteristics of the Miniature Loop Heat Pipe with Non-Condensable Gases," International Journal of Heat and Mass Transfer, 53, pp. 3471- 3482.
  • 10Nikitkin, M. N., Bienert, W. K. A., 1998, "Non Condensable Pipe Operation," SAE Technical B., and Gases and Paper No. Goncharov, Loop Heat 981584.