2011—2012年常州市公共场所集中空调冷却水和冷凝水嗜肺军团菌污染状况 被引量:2

Survey of Legionella pneumophila pollution in cooling water and condensate water of centralized air-conditioning system in public places of Changzhou City from 2011-2012
原文传递
导出
摘要 目的掌握常州市公共场所集中空调冷却水和冷凝水中嗜肺军团菌的污染情况,为预防公共场所中军团菌的传播提供科学依据。方法依据《公共场所集中空调通风系统卫生规范》(2006版)附录A冷却水、冷凝水中嗜肺军团菌检验方法进行检测。结果 2011年41份水样,冷却水、冷凝水中嗜肺军团菌检出率分别为27.5%、41.6%,2012年65份水样,冷却水、冷凝水中嗜肺军团菌检出率分别为38.1%、34.8%,2年的检出率差异无统计学意义;宾馆/饭店56份水样,冷却水、冷凝水中嗜肺军团菌检出率分别为31.4%、28.6%;商场/超市50份水样,冷却水、冷凝水中嗜肺军团菌检出率分别为36.1%、50.0%。2类场所中的检出率差异无统计学意义。总计冷却水71份,冷凝水35份,检出率分别为33.8%、37.1%。结论该市公共场所集中空调冷却水和冷凝水受军团菌污染,检出率较高,存在一定的健康安全隐患,应加强集中空调系统的清洗消毒。 [ Objective ] To understand the status of Legionella pneumophila pollution in cooling water and condensate water of cen- tralized air-conditioning system in public places of Changzhou City, provide scientific basis for preventing the transmission of Legio- nella pneumophila in public places. [ Methods] The study was conducted according to the detecting methods of Legionella pneumo- phila in cooling water and condensate water from Appendix A of the Hygienic specifications of centralized air ventilation system in public places { 2006 Edition). [ Results ] In 2011,41 water samples were detected, and the positive rate of Legionella pneumophila in cooling water and condensate water was 27.5% and 41.6%, respectively. In 2012, 65 water samples were detected, and the positive rate of Legionella pneumophila in cooling water and condensate water was 38.1% and 34.8%, respectively. There was no significant difference between two years. 56 water samples from hotel/restaurant were detected, and the positive rate of cooling wa- ter and condensate water was 31.4% and 28.6% respectively. 50 water samples from shopping mall/supermarket were detected, and the positive rate of cooling water and condensate water was 36.1% and 50.0% respectively. The difference between two places was not significant. 71 samples of cooling water and 35 samples of condensate water were detected, and the positive rate was 33.8% and 37.1% respectively. [ Conclusion] The cooling water and condensate water of centralized air-conditioning system in public places in Changzhou City have been polluted by Legionella pneumophila, with high positive rate, and there are some health and safety hazards. The cleaning and disinfection of centralized air-conditioning system should be strengthened.
出处 《职业与健康》 CAS 2013年第19期2543-2544,共2页 Occupation and Health
关键词 公共场所 军团菌 冷却水 冷凝水 Public place Legionella pneumophila Cooling water Condensate water
  • 相关文献

参考文献5

二级参考文献33

共引文献41

同被引文献99

  • 1于凌琪,王书梅,张致一,王菲,薛志明,刘洪亮.天津市四星级以上宾馆集中空调通风系统微生物污染调查[J].环境与健康杂志,2008,25(1):65-66. 被引量:1
  • 2刘玲,刘一君,郭小玲,沈峻.湖北省公共场所卫生状况调查[J].公共卫生与预防医学,2007,18(1):90-91. 被引量:4
  • 3李泉,付洁,马弋,杨晓敏,谢茂慧.湖北省三市集中式中央空调冷却塔水军团菌污染状况调查[J].公共卫生与预防医学,2007,18(2):50-51. 被引量:5
  • 4中华人民共和国卫生部.WS394-2012公共场所集中空调通风系统卫生规范[S].北京:中国标准出版社,2012.
  • 5Sala-Ferr6 MR. Monitoring of biofilm-associated Legionella pneumophila on different substrata in model cooling tower system[J]. Eur J Clin Microbiol Infect Dis, 2009, 28:153-159.
  • 6Freudenmann M, Kurz S, yon Baum H. Interdisciplinary management of a large Legionella outbreak in Germany [ J ]. Bundesgesundheitsbl, 2011,54:1161-1169.
  • 7曹春远,陈前进,张景平,等.龙岩市2006.2010年部分公共场所水体军团菌污染状况调查分析[c]//第二届传染病防控基础研究与应用技术论坛论文集.2011:181-187.
  • 8高建民,李柱锋,老倩群,等.顺德区公共场所集中空调通风系统微生物污染状况调查与分析[J].中外健康文摘,2013,10(19):8-9.
  • 9Robert LS, Benjamin LW, Leslie E L. The influence of rapid onsite evaluation on the adequacy rate of fine-needle aspiration cytology: a systematic review and mela-analysis[J ]. Am J Cli Pathol,2013, 139: 300-8.
  • 10Campesea C,Bitar D,Jarraud S. Progress in the surveillance and control of Legionella infection in France, 1998-2008 [ J ]. Int J Infect Dis, 2011, 15:30-37.

引证文献2

二级引证文献16

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部