来自国内的 16位消防技术专家对深圳会议展览中心方案消防给水设计进行了技术研讨及论证 ,建议该中心室内高度大于 13m的场所设置消防水炮 ,消防水炮用水量应按同时操作 2台消防水炮计算 ,其他场所地上部分采用快速自动喷水灭火系统 ;
The fire water system design of Shenzhen Convention & Exhibition Center (SZCEC) was discussed and expounded by sixteen well known Chinese fire experts. The specialists suggested that the water jet nozzle system should be installed in door with height above l3 meters, the water flowrate should be calculated according simultaneous operation of two jet nozzles at the same time, the fast response automatic sprinkler systems should be adopted in remaining areas, and that the water volume in storage pool should be enlarged accordingly.