针对辐射型电网母联死区故障的保护改进设计 被引量:8

Protection Improvement Design for Bus Coupler Dead-zone Fault of Radiation Grid
下载PDF
导出
摘要 为确保双母线运行方式下,在母联死区范围内发生故障时,变电站不会全站停电,可以保部分负荷运行,文中对现有母差保护和母联死区保护进行分析研究,对现有母线保护设计方案进行了改进,使其在母线故障时能准确切除故障母线,且在母联死区范围内故障时,也能正确切除母联断路器及与故障相关的母线。最后,通过对母联断路器的动作时间测定,说明此方案可行。 In order to guarantee that no whole transformer substation power outage will occur but partial load is certain to run when the bus coupler dead-zone goes faulty in the double bus operation mode, the differential protection of both the bus and the bus coupler dead-zone is studied. The existing bus protection scheme is improved so that it will act correctly during bus fault. Even though fault should occur in the bus dead-zone, it can still correctly disconnect the bus coupler breaker and the related bus. Finally, by estimating the action time of the bus coupler breaker, the feasibility of the scheme is proved.
出处 《电力系统自动化》 EI CSCD 北大核心 2013年第22期122-124,共3页 Automation of Electric Power Systems
关键词 辐射型电网 短路故障 母联死区 母差保护 radiation grid short-circuit fault bus coupler dead-zone bus differential protection