期刊文献+

发电机定子线棒tanδ影响因素的分析 被引量:2

Influence Factors Analysis of tanδ of Generator Stator Bar
下载PDF
导出
摘要 通过试验和理论计算对影响发电机定子线棒介质损耗的因素进行了分析,结果表明:发电机定子线棒介质损耗因数(tanδ)的大小与线棒导线绝缘结构、防晕结构、线棒几何尺寸、主绝缘厚度等有关,有端部防晕层的线棒其介质损耗比没有防晕层的线棒大;随着防晕层厚度、主绝缘厚度线棒导体尺寸的增加,介质损耗因数将会减小。 The influence factors of the tanδ of generator stator bar were studied by test and theory calcu-lation. The results show that the dielectric loss factor(tanδ) of generator stator bar is related with the insu-lation structure, anti-corona structure, conductor size and main insulation thickness of the stator bar. The dielectric loss factor of the bar with anti-corona coating at the end is bigger than that of the bar without anti-corona coating. With the increase of anti-corona coating thickness, main insulation thickness and con-ductor size, the dielectric loss factor decreases.
出处 《绝缘材料》 CAS 北大核心 2013年第5期48-51,57,共5页 Insulating Materials
基金 国家重大科技专项(2009ZX06004) 黑龙江省科技攻关项目(GC10A203)
关键词 发电机 定子线棒 TANΔ 绝缘结构 防晕结构 generator stator bar tanδ insulation structure anti-corona structure
  • 相关文献

参考文献5

二级参考文献17

  • 1张瑞钧,刘上椿.高压大容量发电机定子线圈槽部电场的数值分析[J].大电机技术,1994(4):26-30. 被引量:9
  • 2郭中源.大型高压电机绝缘耐压性试验方法研究.大型高压电机主绝缘可靠性评定试验方法研究[M].,1985..
  • 3严璋.高压电机绝缘.高电压绝缘[M].,1980..
  • 4张瑞均 吴景泽.空冷汽轮发电机绝缘结构研究[M].,1985..
  • 5唐兴祚.高电压技术[M].重庆:重庆大学出版社,1988..
  • 6西安交通大学主编.电气绝缘结构设计原理[M].北京:水利电力出版社,1987..
  • 7刘耀南 邱昌容.电气绝缘测试技术[M].北京:机械工业出版社,1990..
  • 8Pedersen A, Crichton G C, McAllister I W. Partial discharge detection:theoretical and practical aspects[J]. IEE Proc.-Sci. Meas. Technol.,1995, 142(1): 29-36.
  • 9颜伯昭,刘有.大型电机定子线圈绝缘击穿场强的统计分析[J]大电机技术,1983(04).
  • 10王杰臣.实现非线性多目标函数最优化的一个算法[J]哈尔滨电工学院学报,1982(04).