期刊文献+

改善电网电压水平的发电机励磁系统调差系数优化策略 被引量:20

Optimization Strategy for Generator Excitation System Adjustment Coefficient in Improving Voltage Level of Power Systems
下载PDF
导出
摘要 充分发挥发电机无功电压调节潜力,改善电网电压质量,是电力系统无功电压控制的重要目标。从改善电网全运行电压水平角度出发,提出了发电机励磁系统调差系数优化整定策略。分析了发电机励磁系统调差系数对电网电压的影响,给出了发电机励磁系统调差系数分区整定原则,建立了以系统多运行方式下中枢点电压波动指标为最小的目标函数,以电网潮流约束方程和发电机励磁系统调差系数为控制变量的优化模型,采用粒子群优化算法对其模型进行求解。将优化策略应用到吉林省电网发电机励磁系统调差系数整定中,仿真结果与实际应用均表明,提出的优化整定策略对改善电网运行电压质量,提高发电机无功调节潜力具有重要的意义。 Bringing the potential of generator reactive power regulation into full play and improving the voltage quality of the power grid are key objectives for power system reactive power and voltage control.To improve the power system voltage level,this paper presents an optimization strategy for setting the excitation system adjustment coefficient of the generator.The effect of excitation system adjustment coefficient on power system voltage is studied,and the principle for setting the generator excitation system adjustment coefficient region by region is proposed.An optimization model is developed with the voltage fluctuation index minimum as the objective function,and the power-flow constraint equations and the excitation system adjustment coefficient as control variables.The particle swarm optimization(PSO)algorithm is used in finding the solution.The case studies of Jilin province power system show that the optimization strategy is meaningful in improving the quality of the power system operation voltage and the potential of generator reactive power regulation.
出处 《电力系统自动化》 EI CSCD 北大核心 2013年第23期97-101,共5页 Automation of Electric Power Systems
基金 教育部长江学者和创新团队发展计划资助项目(IRT1114)~~
关键词 无功电压控制 励磁系统 调差系数 控制策略 粒子群优化算法 reactive power and voltage control excitation system adjustment coefficient control strategy particle swarm optimization(PSO)algorithm
  • 相关文献

参考文献17

  • 1IBA K. Reactive power optimization by genetic algorithm[J ]. IEEE Trans on Power Systems, 1994, 9(2) : 685 692.
  • 2HISCOCK N, HAZEL T G. Voltage regulation at sites with distributed generation E J]. IEEE Trans on Industry Applications, 2008, 44(2) 445-454.
  • 3朱桂萍,王树民.电能质量控制技术综述[J].电力系统自动化,2002,26(19):28-31. 被引量:151
  • 4邱军,梁才浩.电厂的电压无功控制策略和实现方式[J].电力系统及其自动化学报,2004,16(2):69-72. 被引量:13
  • 5李志恒,付红军,孙建华,胡扬宇,孙冉,张希全.电厂侧自动电压控制系统电压控制策略的改进[J].电力系统自动化,2011,35(9):95-99. 被引量:13
  • 6DAVIES J B, MIDFORD L E. High side voltage control at manitoba hydro [ C ]// Proceedings of 2000 IEEE Power Engineering Society Summer Meeting: Vol 1, July 16-20, 2000, Seattle, WA, USA: 271-277.
  • 7GB/T7409.3-2007同步发电机励磁系统大、中型同步发电机励磁系统技术要求[S].2007.
  • 8吉林省电力有限公司,东北电力大学.计及电网全运行方式的荔电机励磁系统调差系数整定方法:中国,201210041297[P]2012-07-18.
  • 9NOGUCHI S, SHIMOMURA M. Improvement to an advanced high side voltage control[J]. IEEE Trans on Power Systems, 2006, 21(2): 683-692.
  • 10王琦,周双喜,朱凌志.采用高压侧电压控制改善系统的角度稳定性[J].电网技术,2003,27(6):19-21. 被引量:16

二级参考文献106

共引文献959

同被引文献178

引证文献20

二级引证文献46

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部