期刊文献+

一起变压器近区短路冲击的诊断与分析 被引量:26

Diagnosis and Analysis of Nearby Short-circuit Impact on Transformer
下载PDF
导出
摘要 近区短路冲击是变压器损坏的重要原因,诊断变压器短路冲击后的受损情况并确定检修策略具有重要的意义。介绍了一起变压器近区短路故障导致绕组严重变形的事故。通过对变压器油色谱、三相运行电流、短路阻抗、直流电阻、电容量、频响曲线等数据的综合分析确定了变压器绕组发生严重变形。随后的返厂解体证实了诊断分析方法的有效性。 Nearby short-circuit impact is the main reason of transformer damage, so diagnosing the transformer's status and choosing suitable management strategy are significant. This paper introduces a transformer accident of winding severe deformation caused by nearby short-circuit impact. By analyzing the dates of oil chromatographic, 3 phases' operation currents, short impedance, DC resistance, capacitance and frequency response curves, transformer winding deformation is conformed. The succeeding transformer disassembling indicates the effectiveness of diagnosis and analysis.
出处 《高压电器》 CAS CSCD 北大核心 2013年第12期95-98,103,共5页 High Voltage Apparatus
关键词 短路冲击 变压器 绕组变形 频响法测试 short-circuit impact transformer winding deformation frequency response analysis
  • 相关文献

参考文献11

二级参考文献96

共引文献152

同被引文献158

引证文献26

二级引证文献130

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部