期刊文献+

串级式电压互感器铁磁谐振对介损试验的影响 被引量:2

The influence of ferro-resonance phenomenon of cascade-type voltage transformer on dielectric loss test
下载PDF
导出
摘要 针对关帝变电站220 kVⅠ号母线电压互感器在介质损耗因数测量时试验数据漂移的问题,从铁磁谐振原理出发,分析了串级式电压互感器铁磁谐振对介质损耗因数测量的影响,提出合理可行的解决方案。应用结果表明:通过自备发电机对仪器电压源供电,是一种简单而有效的解决方法。 Aiming at the problem of the test data occur shift when dielectric loss factor measurement of voltage transformer of 220 kV I bus bar in Guandi Substation, based on principle of ferro-reso- nance, analyzes the influence of ferro-resonance phenomenon of cascade type voltage transformer on dielectric loss factor measurement, puts forward feasible solution.The application result shows that it is a simple and effective solution using standby dynamo supply voltage source to the test instrument.
作者 侯峰
出处 《宁夏电力》 2013年第5期20-22,33,共4页 Ningxia Electric Power
关键词 串级式电压互感器 铁磁谐振 介质损耗因数 cascade-type voltage transformer ferro-resonance dielectric loss factor
  • 相关文献

参考文献2

  • 1DL/T474.1-2006,现场绝缘试验实施导则[S].
  • 2DL/T596-1996.电气设备预防性试验规程[S].[S].,..

共引文献17

同被引文献13

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...