摘要
分析某10 kV配电系统的特点,阐述目前电缆故障指示器的故障判断逻辑的优缺点,提出一种适合该电网的故障指示器整定原则,通过ATP/MATLAB软件进行仿真分析,验证了判断逻辑和整定原则的正确性。总结电缆故障指示器在安装、运行维护、使用过程中的经验,提出基于二分法原理的故障查找方法,快速定位电缆故障点,提高了排除配电网故障的工作效率。
The characteristics of 10 kV power distribution system of Hunan area are analyzed and the advantages and disadvantages of fault identifying logics for power cable fault indicator are expounded and a new fault indicator setting principle which is suitable for the grid is put forward. The correctness of the fault identifying logics and setting principle is verified with the ATP/MATLAB software simulation analysis. The experience in the process of the installation operation maintenance and application is summarized out and a fault locating method based on the mathematics principle of dichotomy is proposed to improve the working efficiency of power distribution network fault recovery work.
出处
《湖南电力》
2013年第6期4-6,10,共4页
Hunan Electric Power
关键词
电力电缆
故障指示器
接地系统
可靠性
配电网
二分法
power cable
fault indicator
grounding system
reliability
distribution network